 MITSUBISHI ELECTRIC
Programmable Logic Controllers
40
X
90
IN 0
1 2 3 4 5 6 7
L
N
COM X0 X2 X4 X6 X10 X12 X14 X16 24+ X1 X3 X5 X7 X11 X13 X15 X17
01234567
POWER
IN
10 11 12 13 14 15 16 17
POWER RUN BATT.V
FX 2N-16EX
IN 0
1 2 3 4 5 6 7
FX 2N-32MR
Y0 Y2 Y4 Y6 COM1 Y1 Y3 COM2 Y5 Y7
OUT
01234567 10 11 12 13 14 15 16 17
PROG-E CPU-E
Y10 Y12 Y14 Y16 COM3 Y11 Y13 COM4 Y15 Y17
MELSEC FX0S, FX0N, FX2N
X
87
MITSUBISHI
35
S/S N
L
X26 X16 X20 X22 X24 X6 X10 X12 X14 X21 X23 X25 X27 0V X0 X2 X4 X11 X13 X15 X17 X7 24V X1 X3 X5
0 1 2 3 4 5 6 7 26 27 20 21 22 23 24 25
90
MITSUBISHI
IN
MELSEC FX0N-24MR-ES
POWER RUN BATT.V PROG-E
16 17 10 11 12 13 14 15
0
1
2
3
4
5
6
7
26 27 20 21 22 23 24 25
CPU-E
Y0
COM1 Y1
Y2
Y24 Y26 COM5 Y14 Y16 Y20 Y22 Y25 Y27 Y10 Y12 Y4 Y6 Y15 Y17 Y21 Y23 COM3 Y11 Y13 COM4 Y3 COM2 Y5 Y7
FX2N -48MR
OUT
16 17 10 11 12 13 14 15
T
X27 X25 X23 X21 X26 X24 X22
X
COM L N *
COM X0
X1 X2
X3 X4
X5 X6
X7 X10
X17 X15 X13 X11 X20 X16 X14 X12
7 IN 0 1 2 3 4 5 6
MITSUBISHI
POWER
S/S X1 X3
01 2 3456 7 4 1 0 X5 2 3 X7 5 6 7 X11
X4 X6 X10 X12
X13
X0
X2
IN
67 OUT 0 1 2 3 4 5 0 1 2 3 4 5 6 7 10 1112 13 01 2 3456 7
90
24V+
*
COM0 COM1 COM2
Y3
COM3
Y5
Y7
COM4
Y1
Y3
COM5
Y5
Y7
OUT 0 1 2 3 4 5 6 7
0V 24V Y0 Y1 Y6 Y2 Y3 Y4 COM0 COM1 COM2 COM3 COM4 Y7 Y5
S/S L
100-240VAC
X1 X0 X2
X3 X4
X5 X6
X7
N
7 IN 0 1 2 3 4 5 6
MITSUBISHI
POWER RUN
PROG-E CPU-E
FX0S-14MR-ES
OUT 0 1 2 3 4 5
0V 24V COM0 Y0 COM1 Y1 COM2 Y2 Y3 Y4 Y5 *
35
FX 0N -40ER
Technical Catalogue
1998/99
MELSEC FX
New Items in this Catalogue
MELSEC FX0N
Integration of the new FX2N extension modules and special function modules for the FX0N series
cts w Produ Ne 1998
MELSEC FX2N
The consistent advancement of the proven FX to the FX2N
Accessories Simulation strip for the simulation of digital inputs, Profibus plug
Programming
MX-Scada: process supervision software ProfiMap: Profibus configuration software
Further Publications within the PLC Range
LS EC
AnA, AnN, AnU, QnA Series Technical Catalogue
Product catalogue for programmable logic controllers and accessories for the MELSEC A and Q series (art no. 61747)
ME
N An AA An Q n U An
l Technica es Catalogu
ME
LS
EC
QnAS, AnS Series Technical Catalogue
Product catalogue for programmable logic controllers and accessories for the MELSEC AnS and QnAS series (art. no. 59085)
S An S A Qn
ME
LS
EC
HMI Technical Catalogue
Product catalogue for operator terminals, supervision software and accessories (art. no. 68542)
C MA DU T GO
DIN ISO 9001 / EN 29001
Zertifikat: 09 100 4371
About this product catalogue Texts, figures and diagrams shown in this product catalogue are intended exclusively for explanation and assistance in planning and ordering the programmable logic controllers of the MELSEC FX0S, FX0N and FX2N series and the associated accessories. Only the manuals supplied with the modules are relevant for installation, commissioning and handling of the controllers and the accessories. The information given in this documentation must be read before installation and commissioning of the modules. Should questions arise with regard to the planning of modules described in this product catalogue, do not hesitate to contact the german branch of the MITSUBISHI ELECTRIC EUROPE B.V. in Ratingen or one of its distributors (see cover page). No parts of this product catalogue may be duplicated, stored in an information system or transmitted without prior express written permission from MITSUBISHI ELECTRIC EUROPE B.V.. (c) MITSUBISHI ELECTRIC EUROPE B.V. 12/1998 (2nd issue)
2
MITSUBISHI ELECTRIC
MELSEC FX
CONTENTS
FX FAMILY
SYSTEM DESCRIPTION Introduction of the FX family . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Networks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FX
BASICS
MELSEC FX0S
BASE UNITS Description of system and unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 ACCESSORIES Simulation strip, simulation box . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Program loader. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 TERMINALS AND DIMENSIONS Terminal assignments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
MELSEC FX0N/FX2N
SYSTEM DESCRIPTION Base units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 Extension and special function modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 System specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 BASE UNITS Specifications FX0N. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26 Specifications FX2N. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 EXTENSION UNITS Compact extension units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 Modular extension units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 SPECIAL FUNCTION UNITS Analog modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Counter and positioning module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interface module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Communications modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 39 40 42
ACCESSORIES Memory cassettes and interface converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 PROM adapter, simulation box and simulation strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53 Batteries and connection cables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54 TERMINALS AND DIMENSIONS Terminal assignments of the base units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal assignments of the extension units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Terminal assignments of the special function units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 60 63 66
PROGRAMMING
PROGRAMMING UNITS AND SOFTWARE Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70 Hand-held programming units, cables and EPROM writer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
APPENDIX
Order form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74 Index. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
MITSUBISHI ELECTRIC
3
MELSEC FX
SYSTEM DESCRIPTION The FX Family
The MELSEC FX Family
FX
BASICS
Description
The MELSEC FX family includes a very comprehensive range of base and expansion modules, enabling you to configure a customised system tailored to your precise requirements. Depending on your application and control needs you can choose from the small, attractively-priced, "stand-alone" MELSEC FX0S series, the expandable FX0N series or the more powerful FX2N series. The FX0N and FX2N series are both a good choice for plant installations because their expansion options enable them to grow with the needs of your application. Network integration is also supported, making it possible for your FX controllers to communicate with other PLCs, controllers and MMIs. The PLC systems can be configured as local stations in MITSUBISHI networks (MELSECNET/MINI), and as slave stations in open networks (PROFIBUS/DP). In addition to this, the controllers of the MELSEC FX0N/FX2N series also support integration in multidrop and peer-to-peer network configurations. All FX systems are members of the great MELSEC family of PLCs, in which all systems are compatible with one another.
Special features:
Expandable from 10 - 256 I/Os Compact, robust design Extensive communications support Simple installation Custom configuration for the needs of existing systems Innovative, "future-proof" technology protects your investment Worldwide standards Quality products manufactured in facilities with ISO 9001 certified quality management systems and subject to special manufacturers' standards
MELSEC A / Q MELSEC FX2N
MELSEC FX0S MELSEC AnS/QnAS
MELSEC FX0N
Expandability and power
The MELSEC FX family is highly flexible, enabling fast and efficient configuration and programming for the application at hand. It is the ideal choice, no matter whether you need to install a simple control application requiring up to 30 I/Os (FX0S) or a demanding, complex system with up to 256 I/O points (FX2N). The capacity of the CPUs of the FX0N/FX2N series can be expanded with memory cassettes. Non-volatile memory cassettes with a capacity of up to 16K program steps are available for reliable, long-term storage of your PLC projects. In addition to the other advantages this enables you to switch programs at very short notice, simply by replacing a cassette.
There are three series in the MELSEC FX family, each of which is designed for a different application profile: The FX0S series The MELSEC FX0S series is the inexpensive entry to the MELSEC FX family. With its small dimensions it is also an excellent alternative to relay/contactor control configurations. The FX0N series The CPUs of the FX0N series offer more power than the FX0S series, plus modular expansion capabilities. You can choose from I/O expansion modules and special function modules for a wide variety of applications. The FX2N series The new FX2N series complements the existing FX family and replaces the successful FX series. It gives you the freedom of modular expandability, with a wide selection of expansion modules and special function modules. The FX2N is also one of the fastest PLC systems available, with a
cycle time of just 0,08 s per logical instruction. Thus the FX2N series gives you the most powefull CPU for your apllication and combines all benefits of a compact PLC system with the performance of a modular PLC system.
1,6 - 3,5
2.000
256 30 800 128 1,6
FX0S FX0N FX2N
16.000
No. of inputs/outputs Program steps Cycle time (s)
4
MITSUBISHI ELECTRIC
0,08
MELSEC FX
The FX Family SYSTEM DESCRIPTION
Features
The modular design of the FX0N/FX2N series makes it extremely flexible, enabling it to be used for a very broad range of applications. You can configure tailor-made systems by combining modules from a variety of different categories (see figure). All modules are electrically isolated from their environment with optocouplers for maximum reliability. Digital I/O modules For a variety of signal levels with relay or transistor switches.
FX
BASICS
DIGITAL INPUTS/OUTPUTS
COMMUNICATIONS MODULES
CPU
POSITIONING MODULES
ANALOG INPUTS/ OUTPUTS
Communications modules Interface modules with RS-232/RS-422/RS-485 interfaces for the connection of peripherals and PLC-PLC links. Network modules for Profibus, GSM and for the configuration of proprietary Mitsubishi networks
Positioning modules High-speed counter modules with support for the connection of incremental rotary transducers and positioning modules for servo and stepping motor drives.
Analog I/O modules For processing current/voltage signals and temperature registration with a direct connection option for Pt100 resistance thermometers and thermocouples.
Digital and special function modules - configuration
The options for using digital and special function modules are dictated by CPU used in the system. When calculating the number of special function modules you can use in a system you must take both the number of digital modules and the maximum number of special function modules that can be used into account. The table on the right provides a simplified guide to the number of modules you can use in each system type. More detailed information and the basic principles of system configuration can be found on page 21 ff.
CPU type FX0S FX0N FX2N
System restrictions Stand-alone PLC with 10 / 14 / 20 or 30 I/Os; no special function modules PLC with max.128 I/Os; max.2 special function modules supported PLC with max.256 I/Os; max.8 special function modules
MITSUBISHI ELECTRIC
5
MELSEC FX
SYSTEM DESCRIPTION The FX Family
Handling
FX
BASICS
Installation
Handling and installation of the modules are very simple. All modules are fitted with an integrated DIN adapter for snap-on installation on DIN rail systems. If you wish, the modules can also be installed normally on flat surfaces with screw fastenings. In the FX0N and FX2N series all connections between the CPU's system bus and the expansion and special function modules are made with the standard flat ribbon cable. No other internal system wiring is required for connecting the CPU and modules.
Wiring
All external wiring is connected to the standard cable terminals to the screw terminals on the modules. The entire terminal block has a cover which provides protection against short circuits and inadvertent contact.
Programming
All CPUs have a standardised programming interface for connection of a programming unit or a personal computer. Simple control tasks can be programmed directly using hand-held programming units or the control units of the FX-DU series. In addition to this the CPUs can also be programmed with the MELSEC MEDOC plus software package, which runs on a normal PC. This powerful programming environment can be used to create large application programs conforming to the IEC 1131.3 standard.
Multi-functional interfaces
POWER
Graphic operator terminal
Hand-held programming unit
PC with programming and process supervision software
6
MITSUBISHI ELECTRIC
MELSEC FX
The FX Family SYSTEM DESCRIPTION
Process visualisation
For more effective supervision of machines and processes you can configure a process visualisation system as a hardware or software solution with partial or full graphical support. Process visualisation products available from Mitsubishi include a variety of different operator terminals and the powerful MX-SCADA process visualisation software package.
FX
BASICS
Peripherals
Separate interface modules enable the connection of output devices such as printers and also a variety of input devices such as barcode readers. Optional plug-in interfaces support the connection of additional programming or operator terminals, as well as the realization of various serial links. A range of special communications modules are also available for integration of your PLC systems in a variety of networks.
Base unit FX0N
POWER
FX0N-485ADP
MELSECNET
Base unit FX2N
FX2N232IF
FX2N232IF
FX0N32DP
FX0N16NT
FX 2N -232IF
POWER
SD RD
FX 2N -232IF
POWER
SD RD
Barcode reader Personal computer
Printer
Profibus
MITSUBISHI ELECTRIC
7
MELSEC FX
SYSTEM DESCRIPTION Networks
MELSEC Networks
FX
BASICS
TCP/IP ETHERNET
Ready for immediate operation with the worldwide standard TCP/IP protocol. A PC connected to the Ethernet has full access to all PLCs in the MELSECNET, all the way down to the I/Os on the production level.
MELSECNET/B
A cost-effective alternative within the production level. Enables implementation of easily-manageable configurations for complex applications by means of distributed intelligence.
facturers is also possible. Any twisted-pair cabling can be used as the communications media. MELSEC I/O LINK as a tree structure.
MELSEC FX Peer-to-Peer
The PPN construction enables a network for up to 8 FX2N and FX0N controllers as clients. The max. coverage is up to 500 m. A standard twisted-pair cable can be used as the communications media.
MELSECNET/10 und -NET(II)
Low-cost cabling, brilliantly simple set-up and maximum availability thanks to redundancy and Floating Master. The max. coverage is up to 30 km.
MELSECNET/MINI-S3 MELSEC I/O-LINK
Enables decentralised configurations by linking remote modules to the machine. Integration of devices from other manu-
COMMAND LEVEL TCP/IP ETHERNET
TCP/IP ETHERNET
CONTROL LEVEL MELSECNET/10 MELSECNET(II) MELSECNET/B
AnS/QnAS
AnU/ AnA
MELSECNET/10 MELSECNET/B
AnS/ QnAS
AnU/ AnA
MELSECNET/10 MELSECNET(II)
AnS/ QnAS
AnU/ AnA
AnS/ QnAS
PRODUCTION LEVEL MELSECNET/MINI-S3 MELSEC I/O-LINK MELSEC FX PPN
MELSEC I/O-LINK
MELSECNET/MINI-S3
M ~
MELSEC FX-PPN
M
M
8
MITSUBISHI ELECTRIC
MELSEC FX
Networks SYSTEM DESCRIPTION
Open Networks
MAP 3.0 ETHERNET Interdepartmental data exchange between the command and production levels using a non-proprietary protocol with short throughput times.
Profibus FMS
Communication between equipment from different manufacturers within a single plant. Automatic data exchange with MELSEC networks.
Profibus DP
Enables quick and simple connection of sensors and actuators from different manufacturers to MELSEC PLCs, with data transfer rates of up to 12 Mbaud.
FX
BASICS
COMMAND LEVEL MAP 3.0 ETHERNET
MAP 3.0 ETHERNET
PROF
PROCESS FIELD BUS
I
CONTROL LEVEL Profibus FMS
AnU
BUS
FX0N/FX2N
AnS/QnAS
PRODUCTION LEVEL Profibus DP
PROFIBUS DP
MITSUBISHI ELECTRIC
MAC 90
FX0N/FX2N
MITSUBISHI ELECTRIC
9
MELSEC FX0S
BASE UNITS Description of System
The MELSEC FX0S Series
FX
BASICS
Description
Small Fast Versatile The MELSEC FX0S is the cost-effective entry to the MELSEC family. It combines all the advantages of a PLC system in a very compact package, providing a space- and cost-saving alternative to relay/contactor control systems.
System structure
Base unit with full PLC functionality Integrated power supply unit CPU Maintenance-free EEPROM memory Integrated digital inputs and outputs User-friendly programming systems, including hand-held programming units, IEC 1131.3-compatible programming software and MMIs Accessories
Equipment features
Base units are available in a number of versions with different power supply and output type configurations. You can choose between units with 230 V AC or 24 V DC power supplies and relay or transistor outputs. All the base unit versions have the same basic CPU and performance specifications.
All units feature an analog potentiometer for setpoint value entry and an integrated RUN/STOP switch.
High-speed inputs for fast counting tasks with counting frequencies of up to 7 kHz and interrupt processing capabilities.
The internal service power supply unit for 24 V DC has a capacity of 200 mA.
Square pulse output Integrated pulse outputs for frequencies from 10 to 2000 Hz for controlling stepping motors and outputting pulse-width modulated signals. Integrated serial interface for direct communication with computers.
Flexible installation with the integrated DIN rail adapter and screw fastening hose for mounting on flat surfaces.
Your PLC programs are stored in a maintenance-free EEPROM user memory with a capacity of 800 program steps and a backup battery to protect against power failures. Password access protection facility for effective protection of your intellectual property.
10
MITSUBISHI ELECTRIC
MELSEC FX0S
Description of System BASE UNITS
Description of the Unit
FX
BASICS
Protective cover
Terminal cover Fixing hole Connection of the power supply RUN/STOP switch Analog potentiometer Connection for programming units Protective cover Service voltage source Terminals for digital inputs LEDs for indicating the input statuses LEDs for indicating the operating status LEDs for indicating the output statuses Terminals for digital outputs
Reference Table for Model Designation Code
FX
1
-
14
2
M
3
R
4
E
5a
S
5b
UL
6
The code in detail:
FX = PLC series 1 Designation of the PLC series 2 Number of inputs/outputs e.g. 14 I/Os 3 Description of the unit type: M = base unit E = extension unit EX = modular input extension EY = modular output extension 4 Description of the output type: R = relay T = transistor 5a Power supply: E = 100/240 V AC D = 24 V DC 5b Model variants: S = Inputs selectable as sink or source type Relay outputs SS = Inputs selectable as sink or source type Transistor outputs source type 6 UL = UL certification
MITSUBISHI ELECTRIC
11
MELSEC FX0S
BASE UNITS Specifications
General Specifications
FX
BASICS
General Specifications Ambient temperature Operating temperature Storage temperature Primary power supply Protection Noise durability Dielectric withstand voltage Ambient relative humidity Shock resistance Vibration resistance Insulation resistance Ground Fuse Environment Certifications
Data 0 - 55 C 0 - 55 C -20 - +70 C 24 V DC,200 mA; ripple ratio at maximum load: 5 % IP 20 1000 Vpp with noise generator;1 s at 30 - 100 Hz 1500 V AC,1 min.(500 V AC for direct voltage modules) 35 - 85 % (non-condensing) 10 G (3 times each in 3 directions) 2 G:resistance to vibrations from 10 - 55 Hz for 2 hours along all 3 axes;0.5 G for DIN rail mounting 500 V DC,5 M Class 3 3A Avoid environments containing corrosive gases,install in a dust-free location. UL / CSA / CE / DNV / RINA
Specifications of Base Units
Specifications FX0S-10 MR-DS FX0S-10 MR-ES/UL FX0S-10 MT-DSS FX0S-14 MR-DS FX0S-14 MR-ES/UL FX0S-14 MT-DSS 14 -- -- 24 V DC 5W -- -- 60 A / 1.5 ms 5 -- 8 4.5 1.5
Elektrical data Max. number inputs/outputs 10 10 10 14 14 AC range (+10%, -15%) -- 100-240 V AC -- -- 100-240 V AC Power Frequency at AC Hz -- 50/60 (10%) -- -- 50/60 (10%) supply DC range (+10%, -15%) 24 V DC -- 24 V DC 24 V DC -- Max. input apparent power 4W 30VA 4W 5W 30 VA 100 V AC -- 15 A / 2 ms -- -- 15 A / 2 ms Inrush current 200 V AC -- 25 A / 2 ms -- -- 25 A / 2 ms at ON 24 V DC 60 A / 1.5 ms -- 60 A / 1.5 ms 60 A / 1.5 ms -- Allowable momentary power failure time ms 5 10 5 5 10 External current supply (24 V DC) mA -- 200 -- -- 200 Inputs Integrated inputs 6 6 6 8 8 Min. current for logical 1 mA 4.5 4.5 4.5 4.5 4.5 Max. current for logical 0 mA 1.5 1.5 1.5 1.5 1.5 Response time ms For all units of the MELSEC FX0S series values:10 ms (at time of shipping),adjustable from 0 to 15 ms in steps of 1 ms. Outputs Integrated outputs 4 4 4 6 6 Output Art Relay Relay Transistor Relay Relay Switching voltage (max.) V Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 - 30 V DC - per output A 2.5 2.5 0.5 2.5 2.5 Max. output current - per group* A-- -- 0.8 8 8 - inductive load 80 VA 80VA 12W 80VA 80 VA Max.switching current - lamp load W 100 100 1.5 100 100 Response time ms 10 10 0.2 10 10 Life of contacts (switching times) For all base units of the MELSEC FX0S series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA Mechanical data Weight kg 0.3 0.45 0.3 0.3 0.45 Dimensions (W x H x D) mm 60 x 90 x 47 60 x 90 x 75 60 x 90 x 47 60 x 90 x 47 60 x 90 x 75 Order information Art. no. 55774 55773 55775 55777 55776
6 Transistor 0.5 0.8 12 W 1.5 0.2
0.3 60 x 90 x 47 55778
* The limitation applies only per reference terminal for each group,4 and 8 outputs for relays and 2 and 4 outputs for transistors.Please observe the terminal assignments for the group identification.
12
MITSUBISHI ELECTRIC
MELSEC FX0S
Specifications BASE UNITS
Programming Specifications
System data Program data Program memory Program language Program execution Program protection Number of instructions Cycle period Operands Internal relays Special relays Step relays Timers External setpoint entry via potentiometer Counter High speed counter inputs Data register Filer register Index register Special register Pointer Nesting operands Interrupt inputs Constants
FX
800 steps EEPROM (internal) Stepladder instructions,instruction list Periodical execution of the stored program Password protection with 3 protection levels 20 sequence instructions,2 step ladder instructions,35 applied instructions 1.6 - 3.5 s/log.instruction 512,16 buffered 56 64 56 (100 ms),with 24 to be switched to 10 ms 1 16 inputs,16 Bit 4 counter inputs,32 Bit 32,16 Bit -- 2,16 Bit 27,16 Bit 64 8 4 16 / 32 Bit
BASICS
Specifications of Base Units
FX0S-20 MR-DS 20 -- -- 24 V DC 6W -- -- 60 A / 1.5 ms 5 -- FX0S-20 MR-ES/UL 20 100-240 V AC 50/60 (10%) -- 33VA 15 A / 2 ms 25 A / 2 ms -- 10 200 FX0S-20 MT-DSS 20 -- -- 24 V DC 6W -- -- 60 A / 1.5 ms 5 -- FX0S-30 MR-DS 30 -- -- 24 V DC 8W -- -- 60 A / 1.5 ms 5 -- FX0S-30 MR-ES/UL 30 100-240 V AC 50/60 (10%) -- 35VA 15 A / 2 ms 25 A / 2 ms -- 10 200 16 4.5 1.5 FX0S-30 MT-DSS 30 -- -- 24 V DC 8W -- -- 60 A / 1.5 ms 5 -- 16 4.5 1.5
12 12 12 16 4.5 4.5 4.5 4.5 1.5 1.5 1.5 1.5 For all units of the MELSEC FX0S series values:10 ms (at time of shipping),adjustable from 0 to 15 ms in steps of 1 ms. 8 8 8 Relay Relay Transistor Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 - 30 V DC 2.5 2.5 0.5 8 8 0.8 80 VA 80VA 12W 100 100 1.5 10 10 0.2 For all base units of the MELSEC FX0S series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA 0.45 75 x 90 x 47 55787 0.5 75 x 90 x 75 55779 0.45 75 x 90 x 47 55789 14 Relay 2.5 8 80VA 100 10
14 Relay 2.5 8 80VA 100 10
14 Transistor 0.5 0.8 12W 1.5 0.2
0.45 105 x 90 x 47 55791
0.5 105 x 90 x 75 55790
0.4 105 x 90 x 47 55792
MITSUBISHI ELECTRIC
13
MELSEC FX0S
ACCESSORIES Simulation Strip and Simulation Box
Simulation Strip: Input-SIM: FX0S/FX0N
FX
BASICS
24V 0V 24V 0V
Input-SIM: FXOS/FXON
1
3
5
7
The simulation strip has 8 switches for simulating digital inputs. The strip is directly mounted to the terminals of the unit and fixed with screws to the terminal block. A cable is provided for connecting the strip to the power supply.
The simulation strip can be expanded with another strip for further inputs.
0
2
4
6
X00
-
X07
Specifications Switches Dimensions(WxHxD) Order information
mm Art. no.
Input-SIM: FX0S/FX0N 8 30 x 50 x 15 65081
Simulation Box
The simulation box has 12 switches for simulating digital inputs. It can be used on all controllers of the MELSEC FX familiy.
Specifications Switches Dimensions(WxHxD) Order information
mm Art. no.
Switch Box 12 50 x 100 x 25 3386
14
MITSUBISHI ELECTRIC
MELSEC FX0S
Program Loader ACCESSORIES
Program Loader FX0-10LDR for FX0S in Combination with FX Memory Cassettes
The FX0-10LDR program loader is connected directly to the PLC. It is used for transferring programs between the integrated EEPROM of FX0S units and the memory cassette which is used in the FX0-10LDR. The FX0-10LDR can be used both with the memory cassette and the EEPROM memory of the controller. The program is transferred to the memory set when a memory cassette is inserted. Otherwise, the program is written into the EEPROM of the loader. Moreover, the program can be transferred from the memory of the controller to a memory cartridge inserted in the FX0-10LDR.
FX
BASICS
Specifications Environmental specifications Power supply Current consumption Weight Dimensions (W x H x D) Order information mA kg mm Art. no.
FX0-10LDR Conforms to FX0 base units 5 V DC 5 % (from base unit) 180 0.08 80 x 85 x 28 36644
MITSUBISHI ELECTRIC
15
MELSEC FX0S
TERMINALS + DIMENSIONS Terminal Assignment
Terminal Assignment of Base Units
FX
BASICS
FX0S-10MT-DSS
+
S/S S/S S/S X0 X0
X1 X2 X1 X2 X1 X0 X2
X3 X4 X3 X4 X3 X4
X5
FX0S-14MT-DSS
+
S/S S/S S/S X0 X0
X1 X2 X1 X2 X1 X0 X2
X3 X4 X3 X4 X3 X4
X5 X6 X5 X6 X5 X6
X7
FX0S-10MR-DS
+
X5
FX0S-14MR-DS
+
X7
FX0S-10MR-ES/UL
X5
L
N
FX0S-14MR-ES/UL
X7
L
N
S/S
X1 X0 X2
X3 X4
X5
+
24V DC
-
+
24V DC
-
FX0S-10MT-DSS
0V 24V Y0
Y1 Y2 Y3
+V3
FX0S-14MR-DS
+V0
+V1
+V2
FX0S-10MR-ES/UL
0V Y0 Y1 Y2 Y3 24V COM0 COM1 COM2 COM3 Y0 Y1 Y2 Y3 COM0 COM1 COM2 COM3 Y0 +V0 +V1 Y1 +V2 Y2 Y3 +V3
FX0S-14MR-ES/UL
0V Y0 Y1 Y2 Y4 Y5 24V COM0 COM1 COM2 Y3 Y0 Y1 Y2 Y4 COM0 COM1 COM2 Y3 Y5 Y0 +V0 +V1 Y1 +V2 Y2 Y3 Y4 Y5
FX0S-10MR-DS
FX0S-14MR-DS
FX0S-10MT-DSS
FX0S-14MT-DSS
FX0S-20MT-DSS
+
S/S S/S S/S X0 X0
X1 X2 X1 X2 X1 X0 X2
X3 X4 X3 X4 X3 X4
X5 X6 X5 X6 X5 X6
X7 X11 X13 X10 X12 X7 X11 X13 X10 X12 X7 X11 X13 X10 X12
FX0S-30MT-DSS
+
S/S S/S S/S
S/S X0 S/S X0 S/S X0
X1 X2 X1 X2 X1 X2
X3 X4 X3 X4 X3 X4
X5 X6 X5 X6 X5 X6
X7
X11 X13 X15 X17 X10 X12 X14 X16 X11 X13 X15 X17 X10 X12 X14 X16
FX0S-20MR-DS
+
FX0S-30MR-DS
+
X7
FX0S-20MR-ES/UL
L
N
FX0S-30MR-ES/UL
X7
L
N
X11 X13 X15 X17 X10 X12 X14 X16
S/S
X1
X3
X5
X7
X11
X13
+
24V DC
-
X0
X2
X4
X6
X10
X12
S/S L N
S/S X0
X1 X2
X3 X4
X5 X6
X7 X10
X11 X12
X13 X14
X15 X16
X17
IN
0 1 2 3 4 5 6 7 10 11 12 13
IN 0 1 2 3 4 5 6 7 10 11 1213 14 15 16 17
0S OUT 0 1 2 3 4 5 6 7
0V 24V Y2 Y3 Y4 Y0 Y1 Y6 Y5 COM0 COM1 COM2 COM3 COM4 Y7
0V 24V Y0 COM0 Y1
FX -20MR-DS
FX0S-30MR-ES
OUT 0 1 2 3 4 5 6 7 10 11 1213 14 15
Y2 Y4 COM1 Y3 Y5
Y6 Y10 COM2 Y7 Y11
Y14 Y12 COM3 Y13 Y15
FX0S-20MR-ES/UL
0V Y0 Y1 Y2 Y3 Y4 Y6 24V COM0 COM1 COM2 COM3 COM4 Y5 Y7 Y0 Y1 Y2 Y3 Y4 Y6 Y7 COM0 COM1 COM2 COM3 COM4 Y5 Y0 +V0 +V1 Y1 +V2 Y2 +V3 Y3 +V4 Y4 Y5 Y6 Y7
FX0S-30MR-ES/UL
Y6 Y10 Y12 Y14 Y0 Y2 Y4 0V Y5 COM2 Y7 Y11 COM3 Y13 Y15 24V COM0 Y1 COM1 Y3 Y6 Y10 Y12 Y14 Y0 Y2 Y4 Y5 COM2 Y7 Y11 COM3 Y13 Y15 COM0 Y1 COM1 Y3 Y0 +V0 Y1 Y2 Y4 +V1 Y3 Y5 Y6 +V2 Y7 Y10 Y11 Y12 Y14 +V3 Y13 Y15
FX0S-20MR-DS
FX0S-30MR-DS
FX0S-20MT-DSS
FX0S-30MT-DSS
16
MITSUBISHI ELECTRIC
MELSEC FX0S
Dimensions TERMINALS + DIMENSIONS
Dimensions of Base Units
FX
BASICS
o4,5
X
T
Type FX0S-10MR-ES/UL FX0S-10MR-DS FX0S-10MT-DSS X (in mm) 60 60 60 60 60 60 75 75 75 105 105 105 T (in mm) 75 47 47 75 47 47 75 47 47 75 47 47
S/S
X1
X3
X5
X7
X11
X13
X0
X2
X4
X6
X10
X12
IN
0 1 2 3 4 5 6 7 10 1112 13
FX0S-14MR-ES/UL
105 35
98
90
FX0S-14MR-DS FX0S-14MT-DSS FX0S-20MR-ES/UL FX0S-20MR-DS FX0S-20MT-DSS FX0S-30MR-ES/UL FX0S-30MR-DS FX0S-30MT-DSS
OUT 0 1 2 3 4 5 6 7
0V 24V Y2 Y3 Y4 Y0 Y1 Y6 Y5 COM0 COM1 COM2 COM3 COM4 Y7
MITSUBISHI ELECTRIC
17
MELSEC FX0N/FX2N
SYSTEM DESCRIPTION FX0N Series
The MELSEC FX0N Series
Description
Small-scale PLC offering excellent value for money. Small Fast Universal Modular expansion capability The ability to combine the compact base units with small, modular expansion units and compact I/O expansion units makes the FX0N enormously flexible, giving you a highly economical combination of the cost benefits of compact systems with the versatile expansion capabilities of modular systems.
System structure
Base unit with full PLC functionality Integrated power supply unit CPU Maintenance-free EEPROM memory Integrated digital inputs and outputs Expansion units for adapting the controller system to the required I/O ranges and functionality Configurable as a slave station in peer-topeer and 1:n networks (version 2.00 and above) User-friendly programming systems, including hand-held programming units, IEC 1131.3-compatible programming software and MMIs Accessories
Equipment features
Base units are available in a number of versions with different power supply and output type configurations. You can choose between units with 230 V AC or 24 V DC power supplies and relay or transistor outputs. All the base unit versions have the same basic CPU and performance specifications.
High-speed inputs for fast counting tasks with counting frequencies of up to 5 kHz and interrupt processing capabilities.
Integrated RUN/STOP switch and two analog potentiometers for setpoint value entry.
The base units have integrated, maintenance-free EEPROM user memory for up to 2000 PLC program steps with a backup battery to protect memory contents against power failures. You can also configure password protection to prevent unauthorised access to your programs.
X
7
X
11
X
13
The base units can be expanded for up to 128 I/Os with both modular and compact expansion units.
2 1 0
O U T
X
15
0 1 52 63 14 11 7 15 12 13 4 10
IN
X
5
3 4 5 10
24 O VV C O M Y0 0 C OY M1 1 C OY M2 2 C OY M3 3 YY 45 C OY M6 4 YY 71 0 Y 11
X
3
MS IT /S SU X1 BI P O SH RW UE NR I
PR CP OG UE E
FX O
N
-2 4M R -E S
11
6
7
Integrated pulse outputs for frequencies from 10 to 2000Hz for controlling stepping motors and outputting pulse-width modulated signals. External EPROM or EEPROM memory cassettes for PLC program storage. These memory cassettes are also available in versions with a real-time clock.
18
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
FX2N Series SYSTEM DESCRIPTION
The MELSEC FX2N Series
Description
The MELSEC FX2N series has the most powerful CPUs in the MELSEC FX family. It combines the advantages of a compact PLC with the performance boost of modular PLC systems: One of the fastest PLC systems available, with a program cycle period of just 0.08 s per logical instruction Powerful basic instruction set with an additional 125 dedicated instructions for fast, efficient programming of complex tasks Simple handling Integrated real-time clock Integrated PID controller with autotuning facility Floating-point math, square root function Big memory capacity for up to 16000 PLC program steps
System structure
Base unit with full PLC functionality Integrated power supply unit CPU Integrated digital inputs and outputs Supplementary add-in function boards for adapting the controller system to the required I/O ranges and functionality Integration as a master or slave station in peer-to-peer networks and as a slave station in 1:n networks Efficient, powerful user-friendly programming with hand-held programming units, MMIs and IEC 1131.3compatible programming software Accessories
Equipment features
A basic MELSEC FX2N PLC system consists of a stand-alone base unit. Just like the modules in the other FX series these base units contain all the PLC components, including the CPU, memory and the I/O control circuitry. All the base unit versions in the series have the same basic CPU and performance specifications. A total of 20 different base units are available, with between 16 and 128 I/Os in their standard configuration. Versions are available with 230 V AC power supplies (24 V DC available from Summer 1998) and relay or transistor outputs. The digital inputs are powered by the integrated power supply unit. Removable terminal blocks make reconfiguration for new tasks very quick and easy. A range of powerful expansion and special function modules enable you to configure your setup flexibly to provide the precise functionality and I/O specifications required by your application. You can add I/Os to the base units by installing modular expansion units with 8 or 16 additional I/Os each. You can also add a range of compact expansion units and special function modules - for example for processing analog signals, for positioning tasks and to provide additional interfaces.
Integrated high-speed counter inputs for processing fast input signals. For example, you can configure two 60 kHz counters or four 10 kHz counters. Interrupt processing is also handled via the inputs.
RAM/EEPROM memory for up to 16000 PLC program steps gives you plenty of reserve, even for big, complex applications. The base units can be expanded to provide configurations with up to 256 inputs and outputs with modular and compact expansion units.
Add-in function boards can be installed in the PLC to provide a second RS-485 / RS-422 / RS-232 communications interface for programming or network configurations. An add-in function board with 8 analog potentiometers is also available.
PO
6 X1
R U N BA TT .V PR
2 3 Y1 6 Y1 5 4 Y1 Y1 M4 CO
W
ER
0 10 1 11 2 12 3 13 4 14 5 15 6 16 7 17
2 X1 0 X1 X6 X4 X2
IN
M IT SU BI SH I
0 10 1 11 2 12 3 13 4 14 5 15 6 16 7 17
X0 M CO
7 Y1
OU
T
-3 2M R
Y1 1 0 Y1 Y1 M3 CO Y7
FX 2
N
Y Y5 Y4 M2 CO YO M1 CO Y2 Y1 Y3
6
CP
U
4 X1
O E
G
E
Integrated real-time clock with year, month and time
Integrated serial interface for direct communication with computers
An integrated RUN/STOP switch is available
Integrated pulse outputs for frequencies from 10 to 20000 Hz with deceleration and acceleration ramps for controlling stepping motors and outputting pulse-width modulated signals.
MITSUBISHI ELECTRIC
19
MELSEC FX0N/FX2N
SYSTEM DESCRIPTION Operator Controls
Description of Units FX0N series
Protective cover Connection of the power supply Fixing hole Slot for memory cassettes Communications bus LEDs for indicating the operating status Terminals for service voltage source Terminals for digital outputs Finger protection Housing cover Protective cover LEDs for indicating the input statuses Terminals for digital inputs Extension bus Analog potentiometer RUN/STOP switch Connection for programming units Protective cover LEDs for indicating the output statuses
FX2N series
Connection of the power supply Fixing hole Extension connector for adapter units Backup battery Connection for programming units RUN/STOP switch Detachable terminal strip for digital outputs Housing cover
Slot for memory cassettes Detachable terminal strip for digital inputs LEDs for indicating the input statuses LEDs for indicating the operating status Connection for extensions Protective cover for the extension bus LEDs for indicating the output statuses Protective cover
20
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Combination Options SYSTEM DESCRIPTION
Combining Units from Different Series
The I/O expansion modules and special function modules from the two series can be combined at will, subject to the restrictions imposed by the differences between the systems. For example, you can use all the modules for the FX0N series in combination with a base unit from the FX2N series. Combined use of modules from both series is also possible. A special conversion adapter is available (designation: FX2N-CNV-IF) for connecting modules from the old FX series to the base units of the FX2N series. The tables and figures below show the restrictions and other special requirements that apply for combined use of modules from different systems.
Series Restrictions Special requirements
FX0N All special functions modules are applicable with CPU version 2.00 or higher --
FX2N -- Modules FX0N-485ADP and FX0N-232ADP connect to the left of the CPU and require function board FX2N-CNV-BD for connection to the FX2N.
Base units
Modular expansions
Compact expansions
Special function Special function modules modules
FX0N
-24MR
FX0N
-8EX
FX0N
-40ER
FX0N
-32NT
FX2N
-4AD
FX2N
-32MR
FX2N
-16EX
FX2N
-32ET
FX0N
-3A
FX0N
-32NT
FX2N
-1HC
i
FX2N
-1PG
i
i Can also be used with MELSEC FX0N and CPU version 2.00 or higher
CPU version 2.0
All base units of the FX0N series are now shipped with the 2.0 version of the CPU. If you already have an FX0N base unit you can check the CPU version by comparing the serial number to the entries in the table on the right.
Version 1.30 Up to no.78 Up to no.79 Version 2.00 From no.78 From no.7Xllll Remark For all FX0N base units except FX0N-60MR-DS For FX0N-60MR-DS only
MITSUBISHI ELECTRIC
21
MELSEC FX0N/FX2N
SYSTEM DESCRIPTION Extension and Special Function Modules
Special Function Modules MELSEC FX0N/FX2N
FX0N FX2N
FX0N -32NT-DP
POWER DC RUN
RDA RDB SDA SDB SG
BF
DIA
Left-side installation
Right-side installation
Right-side installation
Installation in base unit
In general
Additional special function modules are available that make it possible to extend the capacity of the basic and extension units of your PLC system. There are three basic categories of special function modules: Modules that occupy digital I/Os (connected on the right hand side of the controller unit). These are the digital compact and modular extension units as well as the special function modules. Modules of the FX0N series that do not occupy any digital I/Os (connected on the left hand side of the controller unit). These are the FX0N-232ADP and the FX0N-485ADP. Internal adapter boards for the FX2N series. These expansion units are installed directly in the controller and do not occupy any digital I/Os.
FX0N series configuration notes
The configuration specifications for the FX0N series permit connection of the following combinations of expansion units to the base units: a maximum of 2 special function modules or digital expansion modules with up to 32 inputs and outputs (4 x 8 I/Os or 2 x 16 I/Os) or one special function module and one digital expansion module with up to 16 inputs and outputs (2 x 8 I/Os or 1 x 16 I/Os) The same configuration specifications apply for the connection of compact expansion modules. Provided you observe these rules the system's power supply will also be adequate to provide the 24 V DC input required by the FX0N-232ADP communications module. Similarly, the power supply for MMIs such as the FX-DU control panels and MAC operator terminals is provided via the system's 5 V bus.
FX2N series configuration notes
The configuration specifications for the FX2N series permit connection of the following combinations of units: A maximum of 8 special function modules or Digital expansion modules with up to 256 I/Os Please note that it is important to calculate the connected load to ensure that the internal 5 V bus has adequate capacity for the installed modules. When using special function modules you must also check the 24 V power supply load - the necessary 24 V power can be drawn from the internal service power supply, but it may be necessary to complement this with an external power supply in some configurations. You can calculate the precise power load with the values provided in the table on the next page.
22
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Power Consumption SYSTEM DESCRIPTION
Calculation of the Power Consumption
The power consumption figures on the 5 V DC bus for the special function modules are shown in the specifications tables on the following pages. The maximum permissible currents on the 5 V DC bus are shown in the table below.
Module FX2NFX2NM -ES(ESS) E -ES(ESS) Max. current on 5 V bus 290 mA 690 mA
FX0N FX2N
through FX2N-32M -E ,
Max. residual current values (in mA) for FX2N-16M -E FX2N-32E -E for the permissible configuration
24 Number of additional outputs 16 8 0 25 100 175 250 0 50 125 200 8 0 75 150 16 25 100 24 50 32
Number of additional inputs
Max. residual current values (in mA) for FX2N-48M -E FX2N-48E -E for the permissible configuration
48 40 Number of additional outputs 32 24 16 8 0 10 85 160 235 310 385 460 0 35 110 185 260 335 410 8 60 135 210 285 360 16 10 85 160 235 310 24
through FX2N-128M -E
,
The residual currents for the 24 V DC service voltage at different input/output configurations are shown in the tables on the right. Special function modules have to be supplied external, if the residual current for the service voltage is not satisfying. A maximum of 256 I/Os are possible.
35 110 185 260 32 60 135 210 40 10 85 160 48 35 110 56 60 64
Number of additional inputs
Sample calculations
The table below and on the right show different examples for sample power calculation for a PLC system. The current values for the special function modules can be found in the specifications on the following pages. Comparison with the current value tables show that the calculated figures for the 5 V bus lie within the allowable ranges. In the example below all units can be supplied sufficiently with the internal 24 V power supply.
Module FX2N-80MR-ES FX2N-4AD FX2N-4DA FX2N-232IF No. 1 3 2 1 24 V DC calculation Current / module 460 mA 50 mA 200 mA 80 mA Calculation +460 mA -150 mA -400 mA -80 mA
-170 mA !!!
FX0N FX2N
5 V DC calculation Current / module +290 mA 30 mA 30 mA 40 mA Total current +290 mA -90 mA -60 mA -40 mA
290 - 190 mA
Result:
100 mA (OK !)
An external 24 V power supply has to be added In the example above.
Module FX2N-48MR-ES/UL FX2N-16EYR-ES/UL FX2N-8EX-ES/UL FX2N-8EYR-ES/UL FX0N-3A
No. X 1 1 1 1 1 24 -- 8 -- --
Number of I/Os Y 24 16 -- 8 -- X/Y -- -- -- -- 8 Total
24 V DC calculation Total current
5 V DC calculation Current / module 290 mA Total current +290 mA 0 mA 0 mA 0 mA -30 mA
+260 mA (OK!)
X=8 Y = 24
(c)
+185 mA
-- -- --
-90 mA
+95 mA (OK!)
30 mA
FX2N-32ER-ES/UL FX2N-16EX-ES/UL FX2N-4AD FX2N-1HC
1 1 1 1 Result:
16 16 -- --
16 -- -- --
64 + 64 + 24 = 152 ! (< 256) OK!
-- -- 8 8 X = 16 Y=0
+150 mA 30 mA 0 mA
+120 mA (OK!)
690 mA -- 50 mA 40 mA
+690 mA 0 mA -30 mA -90 mA
+570 mA (OK!)
(c)
Total no. of I/Os which are connected to a base unit to caculate the max. residual current values (see tables)
see tables above (max. residual current values)
MITSUBISHI ELECTRIC
23
MELSEC FX0N/FX2N
SYSTEM DESCRIPTION Possible Configurations
Configuration Example FX0N
IN
The adressing of the special function modules is independent of the addressing of the digital inputs/outputs. An example of adressing is shown in the table on the right.
Configuration Inputs X Number OutputsY Special function modules Inputs X Adresses OutputsY Special function modules
FX0N -24MR-ES 14 10 -- 0 - 15 0 - 11
FX0N -8EX 8 -- -- 20 - 27 --
FX0N -8EYR -- 8 -- -- 20 - 27
FX0N -40ER-ES 24 16 -- 30 - 57 30 - 47
FX0N -3A -- -- 8 -- -- No.0
Total 46 34 8
88
Configuration Example FX2N
OUT
FX 0N -32NT-DP
POWER DC RUN
BF
DIA
FX 2N-4DA
I+
OUT
D/A
The adressing of the special function modules is independent of the addressing of the digital inputs/outputs. An example of adressing is shown in the table on the right.
Configuration Inputs X Number OutputsY Special function modules Inputs X OutputsY Special function modules
FX2N -32MR-ES 16 16 -- 0 - 17 0 - 17
FX2N -16EYR -- 16 -- -- 20 - 37
FX0N -32NT/DP -- -- 8 -- -- No.0
FX2N -32ER-ES 16 16 -- 20 - 37 40 - 57
FX0N -4DA -- -- 8 -- -- No.1
Total 32 48 16
Adresses
96
24
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications SYSTEM DESCRIPTION
Environmental Specifications
General specifications
Ambient temperature Operating temperature Storage temperature Servcie power supply Protection Noise durability Dielectric withstand voltage Ambient relative humidity Shock resistance Vibration resistance Isulation resistance Ground Fuse Environment Certifications
FX0N FX2N
Data 0 - 55 C 0 - 55 C -20 - +70 C 24 V DC,200 mA (FX0N);250/460 mA (FX2N) ripple ratio at maximum load: 5 % IP 20 1000 Vpp with noise generator;1 ms at 30 - 100 Hz 1500 V AC,1 min. 35 - 85 % (non-condensing) 10 G (3 times in 3 directions) 2 G:resistance to vibrations from 10 - 55 Hz for 2 hours along all 3 axes;0.5 G for DIN rail mounting 500 V DC,5 M Class 3 FX0N:3 A (all units),FX2N:3,15 A (up to FX2N-32 ); 5 A (from FX2N-48 ) Avoid environments containing corrosive gases,install in a dust-free location. FX0N:UL/CSA/CE/DNV/RINA,FX2N:UL/CSA/CE/DNV/LL
General Specifications
System specifications Program data I/O points (adresses) Address range Program memory Cycle period Number of instructions Programming language Program execution Program protection Operands Internal relays Special relays Step ladder Timer Ext. preset value via potentiometer Counter High-speed counter Real-time clock Data register File register Index register Special register Pointer Nestings Interrupt inputs Constants FX0N 128 Max.84 inputs X0-X123,max.64 outputs Y0-Y77 2000 steps EEPROM (internal), EEPROM/ EPROM cassettes (optional) Min.1.6 s / logical instruction 20 sequence instructions,2 stepladder instructions, 42 applied instructions Stepladder,instruction list Cyclical execution,refresh mode processing Password protection with 3 protection levels 512 (128 buffered) 57 128 64 2 32 (16 buffered) Max.4 -- 256 (128 buffered) Max.1500 2 28 64 8 Max.4 16 bits:K:-32768 to +32767,hex:0-FFFF 32 bits:K:2147483648 to +2147483647,hex:0-FFFF FFFF FX2N
FX0N FX2N
256 Max.256 inputs X0-X377,max.256 outputs Y0-Y377 8000 steps RAM (internal), 4000 steps EPROM/EEPROM cassettes (optional), 16000 steps RAM cassettes (optional), for further details refer to p.52 16000 steps EEPROM cassettes (optional) 0.08 s / logical instruction 27 sequence instructions,2 stepladder instructions,18 verify instructions, 107 applied instructions Stepladder,instruction list,SFC Cyclical execution,refresh mode processing Password protection with 3 protection levels 3072 256 1000 256 -- 256 6 single phase inputs (4 double phase inputs) Year,month,day,hour,minut,second,weekday 8000 Max .7000 (parameter editable) 16 256 128 8 6 16 bits:K:-32768 to +32767,hex:0-FFFF 32 bits:K:2147483648 to +2147483647,hex:0-FFFF FFFF 32 bits floating point:0, 1.175 x 10-38 to 3.403 x 10-38
MITSUBISHI ELECTRIC
25
MELSEC FX0N/FX2N
BASE UNITS Specifications
Specifications of Base Units
FX0N FX2N
Base Units FX0N
The FX0N series base units are available with 24, 40 or 60 input/output points. It is possible to choose between relay and transistor output type.
FX
BASICS
Special features:
Integrated serial interface for communication between PC and HMI Standard programming unit interface LEDs for indicating the input and output status Detachable terminal blocks at units with 40 and 60 I/Os Slot for memory cassettes and real-time clock
Specifications
FX0N-24 MR-DS
FX0N-24 MR-ES/UL
FX0N-24 MT-DSS
FX0N-40 MR-DS
FX0N-40 MR-ES/UL
FX0N-40 MT-DSS 40 -- -- 24 V DC 20W -- -- 60 A / 50 s 10 -- 24 3.5 1.5
Electrical data Integrated inputs/outputs 24 24 24 40 40 AC range (+10%, -15%) -- 100-240 V AC -- -- 100-240 V AC Power Frequency at AC Hz -- 50/60 (10 %) -- -- 50/60 (10 %) supply DC range (+20%, -15%) 24 V DC -- 24 V DC 24 V DC -- Max. input apparent power 18W 50VA 18 W 20 W 50VA 100 V AC -- 30 A / 5 ms -- -- 30 A / 5 ms Inrush -- 50 A / 5 ms -- -- 50 A / 5 ms current at ON 200 V AC 24 V DC 60 A / 50 s -- 60 A / 50 s 60 A / 50 s -- Allowable momentary power failure time 10 10 10 10 10 External service power supply (24 V DC) -- 200 -- -- 200 Inputs Integrated inputs 14 14 14 24 24 Min. current for logical 1 mA 3.5 3.5 3.5 3.5 3.5 Max. current for logical 0 mA 1.5 1.5 1.5 1.5 1.5 Response time For all base units of the MELSEC FX0N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms Outputs Integrated outputs 10 10 10 16 16 Output type Relay Relay Transistor Relay Relay Max. switching voltage V Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 - 30 V DC - per output A2 2 0,5 2 2 Max. output current - per group* A-- -- 0,8 -- -- VA 80 80 12 80 80 Max. switching - inductive load power - lamp load W 100 100 1,5 100 100 Response time ms 10 10 < 0,2 10 10 Life of contacts (switching times) For all base units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA Mechanical data Weight kg 0.6 0.6 0.6 0.75 0.75 Dimensions (W x H x D) mm 130 x 90 x 87 130 x 90 x 87 130 x 90 x 87 150 x 90 x 87 150 x 90 x 87 Order information Art. no. 66657 66656 66658 66660 66659
16 Transistor 0,5 0,8 12 1,5 < 0,2
0.75 150 x 90 x 87 66661
* Thislimitation applies only per reference terminalfor eachgroup,4 and8 outputs for relaysand 2 and 4 outputsfor transistors.Please observe the terminal assignments for thegroup identification.
26
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications BASE UNITS
Specifications of Base Units
FX0N FX2N
FX
BASICS
Specifications Electrical data Integrated inputs/outputs AC range (+10%, -15%) Power Frequency at AC supply DC range (+20%, -15%) Max. input apparent power 100 V AC Inrush current at ON 200 V AC 24 V DC Allowable momentary power failure time Externalservicepowersupply(24VDC) Inputs Integrated inputs Min. current for logical 1 Max. current for logical 0 Response time Outputs Integrated outputs Output type Max. switching voltage - per output Max. output current - per group* Max. switching - inductive load power - lamp load Response time Life of contacts (switching times) Mechanical data Weight Dimensions (W x H x D) Order information
FX0N-60 MR-DS 60 -- Hz -- 24 V DC 24W -- -- 60 A / 50 s 10 mA --
FX0N-60 MR-ES/UL 60 100-240 V AC 50/60 (10 %) -- 60 VA 30 A / 5 ms 50 A / 5 ms -- 10 200
FX0N-60 MT-DSS 60 -- -- 24 V DC 24W -- -- 60 A / 50 s 10 --
36 36 36 mA 3.5 3.5 3.5 mA 1.5 1.5 1.5 For all base units of the MELSEC FX0N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms 24 24 Relay Relay Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 - 30 V DC 2 2 -- -- 80 80 100 100 10 10 For all base units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80VA 0.9 185 x 90 x 87 66662 24 Transistor 0.5 0.8 12 1.5 < 0.2
V A A VA W ms
kg 0.9 mm 185 x 90 x 87
0.9 185 x 90 x 87 66664
Art. no. 66663
* Thislimitation appliesonly per reference terminal for each group, 4 and 8 outputs for relaysand 2 and 4 outputsfor transistors. Please observe the terminal assignments for thegroupidentification.
MITSUBISHI ELECTRIC
27
MELSEC FX0N/FX2N
BASE UNITS Specifications
Specifications for Base Units
FX0N FX2N
Base Units FX2N
The FX2N series base units are available with 16, 32, 48, 64, 80 or 128 input/output points. It is possible to choose between relay and transistor output type.
FX
BASICS
Special features:
Exchangable interface modules for direct mounting into a base unit Standard programming unit interface LEDs for indicating the input and output status Detachable terminal blocks Slot for memory cassettes for up to 16 k steps PLC program Integrated real-time clock
Specifications Electrical data Integrated inputs/outputs AC range (+10%,-15%) Power Frequency at AC supply DC range (+20 %, -30 %) Max. input apparent power AC 100 V Inrush current at ON AC 200 V Allowable momentary power failure time External service power supply (24 V DC) Power supply int. bus (5 V DC) Inputs Integrated inputs Input current X0X7 / X10 Min. current for logical 1 X0X7 / X10 Max. current for logical 0 Isolation Response time Outputs Integrated outputs Output type ON voltage (max.) - per output Max. output current - per group Max. switching - inductive load power - lamp load Response time Life of contacts (switching times) Mechanical data Weight Dimensions (W x H x D) Order information
FX2N-16 MR-ES/UL 16 100-240 V AC Hz 50/60 (10 %) -- 30VA 40 A < 5 ms 60 A < 5 ms ms 10 mA 250 mA 290 8 mA 7 / 5 mA 4.5 /3.5
FX2N-16 MT-ESS/UL 16 100-240 V AC 50/60 (10 %) -- 30VA 40 A < 5 ms 60 A < 5 ms 10 250 290 8 7/5 4.5 / 3.5
FX2N-32 MR-DS 32 -- -- 24 V DC 25W -- -- 5 -- 290 16 7/5 4.5 / 3.5
FX2N-32 MR-ES/UL 32 100-240 V AC 50/60 (10 %) -- 40 VA 40 A < 5 ms 60 A < 5 ms 10 250 290 16 7/5 4.5 / 3.5
FX2N-32 MT-DSS 32 -- -- 24 V DC 25 W -- -- 5 -- 290 16 7/5 4.5 / 3.5
FX2N-32 MT-ESS/UL 32 100-240 V AC 50/60 (10 %) -- 40VA 40 A < 5 ms 60 A < 5 ms 10 250 290 16 7/5 4.5 / 3.5
mA 1.5 1.5 1.5 1.5 1.5 1.5 Photocoupler isolation between input terminals and PC power for all base units. For all base units of the MELSEC FX2N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms (REFF,FNC51 = 0 - 60 ms) 8 8 16 16 Relay Transistor Relay Relay Generally for relay version:< 250 V AC,< 30 V DC;for transistor version:5 - 30 V DC 2 0.5 2 2 -- 0.8 -- -- 80 12 80 80 100 1.5 100 100 10 < 0.2 10 < 0.2 For all base units of the FX2N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA 0.6 130 x 90 x 87 65551 0.65 150 x 90 x 87 66620 0.65 150 x 90 x 87 65553 16 Transistor 0.5 0.8 12 1.5 < 0.2 16 Transistor 0.5 0.8 12 1.5 < 0.2
A A W W ms
kg 0.6 mm 130 x 90 x 87
0.65 150 x 90 x 87 66621
0.65 150 x 90 x 87 65554
Art. no. 65550
This limitationappliesonly per referenceterminal for each group,4 and8 outputs for relaysand 2 and 4 outputsfor transistors. Please observe the terminal assignmentsfor the group identification. Available until07/1998
28
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications BASE UNITS
Specifications of Base Units
FX0N FX2N
FX
BASICS
FX2N-48 MR-DS 48 -- -- 24 V DC 30 W -- -- 5 -- 290 24 7/5 4.5 / 3.5
FX2N-48 MR-ES/UL 48 100-240 V AC 50/60 (10 %) -- 50 VA 40 A < 5 ms 60 A < 5 ms 10 460 290 24 7/5 4.5 / 3.5
FX2N-48 MT-ESS/UL 48 100-240 V AC 50/60 (10 %) -- 50VA 40 A < 5 ms 60 A < 5 ms 10 460 290 24 7/5 4.5 / 3.5
FX2N-48 MT-DSS b 48 -- -- 24 V DC 30W -- -- 5 -- 290 24 7/5 4.5 / 3.5
FX2N-64 MR-DS b 64 -- -- 24 V DC 35W -- -- 5 -- 290 32 7/5 4.5 / 3.5
FX2N-64 MR-ES/UL 64 100-240 V AC 50/60 (10 %) -- 60VA 40 A < 5 ms 60 A < 5 ms 10 460 290 32 7/5 4.5 / 3.5
FX2N-64 MT-DSS b 64 -- -- 24 V DC 35 W -- -- 5 -- 290 32 7/5 4.5 / 3.5 1.5
FX2N-64 MT-ESS/UL 64 100-240 V AC 50/60 (10 %) -- 60 VA 40 A < 5 ms 60 A < 5 ms 10 460 290 32 7/5 4.5 / 3.5 1.5
1.5 1.5 1.5 1.5 1.5 1.5 Photocoupler isolation between input terminals and PC power for all base units. For all base units of the MELSEC FX2N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms (REFF,FNC51 = 0 - 60 ms) 24 24 24 24 Relay Relay Transistor Transistor Generally for relay version:< 250 V AV,< 30 V DC;for transistor version:5 - 30 V DC 2 2 0.5 0.5 8 8 0.8 0.8 80 80 12 12 100 100 1.5 1,5 10 10 < 0.2 <0.2 For all base units of the FX2N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA 0.85 182 x 90 x 87 66622 0.85 182 x 90 x 87 65560 0.85 182 x 90 x 87 65561 0,85 182 x 90 x 87 66623 32 Relay 2 8 80 100 10 32 Relay 2 8 80 1.5 10
32 Transistor 0.5 0.8 12 1.5 < 0.2
32 Transistor 0.5 0.8 12 1.5 < 0.2
1.0 220 x 90 x 87 66624
1.0 220 x 90 x 87 65562
1.0 220 x 90 x 87 66626
1.0 220 x 90 x 87 65563
This limitation applies only per reference terminal for each group, 4 and 8 outputs for relays and 2 and 4 outputs for transistors. Please observe the terminal assignments for the group identification. Available until 07/1998
MITSUBISHI ELECTRIC
29
MELSEC FX0N/FX2N
BASE UNITS Specifications
Specifications of Base Units
FX0N FX2N
FX
BASICS
Specifications Electrical data Integrated inputs/outputs AC range (+10%,-15%) Power Frequency at AC Hz supply DC range ( 8 V) Max. input apparent power 100 V AC Inrush current at ON 200 V AC Allowable momentary ms power failure time Externalservice power supply (24 V DC) mA Power supply int. bus (5 V DC) mA Inputs Integrated inputs Input current X0X7 / X10 mA Min. current for logical 1 mA X0X7 / X10 Max. current for logical 0 mA Isolation Response time Outputs Integrated outputs Output type ON voltage (max.) - per output A Max. output current - per group* A W Max. switching - inductive load power - lamp load W Response time ms Life of contacts (switching times) Mechanical data Weight kg Dimensions (W x H x D) mm Order information
FX2N-80 MR-DS 80 -- -- 24 V DC 40W -- -- 5 -- 290 40 7/5 4.5 / 3.5
FX2N-80 MR-ES/UL 80 100-240 V AC 50/60 (10 %) -- 70 VA 40 A < 5 ms 60 A < 5 ms 10 460 290 40 7/5 4.5 / 3.5
FX2N-80 MT-ESS/UL 80 100-240 V AC 50/60 (10 %) -- 70VA 40 A < 5 ms 60 A < 5 ms 10 460 290 40 7/5 4.5 / 3.5
FX2N-80 MT-DSS b 80 -- -- 24 V DC 40 W -- -- 5 -- 290 40 7/5 4.5 / 3.5
FX2N-128 MR-ES/UL 128 100-240 V AC 50/60 (10 %) -- 100 VA 50 A < 7 ms 70 A < 7 ms 10 460 290 64 7/5 4.5 / 3.5
FX2N-128 MT-ESS/UL 128 100-240 V AC 50/60 (10 %) -- 100VA 50 A < 7 ms 70 A < 7 ms 10 460 290 64 7/5 4.5 / 3.5
1.5 1.5 1.5 1.5 1.5 1.5 Photocoupler isolation between input terminals and PC power for all base units For all base units of the MELSEC FX2N series values:10 ms (at time of shipment),partly adjustable between 0 and 15 ms (REFF,FNC51 = 0 - 60 ms) 40 40 40 40 Relay Relay Transistor Transistor Generally for relay version:< 250 V AC,< 30 V DC;for transistor version:5 - 30 V DC 2 2 0.5 0.5 8 8 0.8 0.8 80 80 12 12 100 100 1.5 1.5 10 10 < 0.2 < 0.2 For all base units of the FX2N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA 1.2 285 x 90 x 87 1.2 285 x 90 x 87 65564 1.2 285 x 90 x 87 65565 1.2 285 x 90 x 87 66628 64 Relay 2 8 80 100 10 64 Transistor 0.5 0.8 12 1.5 < 0.2
1.8 350 x 90 x 87 65566
1.8 350 x 90 x 87 65567
Art. no. 66627
Thislimitation applies only per reference terminalfor each group,4 and 8 outputsfor relays and2 and4 outputs for transistors.Pleaseobservetheterminal assignmentsfor the group identification. Available until 07/1998
30
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
The Extension Concept SYSTEM DESCRIPTION
Digital Inputs/Outputs
Various modular and compact extension units are available for extending the MELSEC MELSEC FX0N/FX2N base units. The modular extension units contain only digital inputs/outputs and no separate power supply, while compact extension units contain a larger number of inputs/outputs and an integrated power supply unit for supplying the system bus and the digital inputs. The large number of possible combinations of base and extension units of the MELSEC FX0N/FX2N ensure that the best possible economical solution is found for every application. Owing to the capacity of the internal power supply unit of the respective base unit or of the compact extension unit, modular expandability of the controller is possible with the help of a protected flat cable. A base unit can be extended by a maximum of 128 (FX0N series) or 256 (FX2N series) external inputs/outputs by means of these extension units. FX0N and FX2N series extension units can be combined without any problems.
FX
BASICS
IN
Compact extension units
Module type FX0N-40ER-ES/UL FX0N-40ER-DS FX0N-40ET-DSS Inputs 24 24 24 Outputs 16 16 16 Output type Relay Relay Transistor Module type FX2N-32ER-ES/UL FX2N-32ET-ESS/UL FX2N-48ER-ES/UL FX2N-48ET-ESS/UL FX2N-48ER-DS FX2N-48ET-DSS Inputs 16 16 24 24 24 24
FX0N FX2N
Outputs 16 16 24 24 24 24 Output type Relay Transistor Relay Transistor Relay Transistor
Modular extension units
Module type FX0N-8EX-ES/UL FX0N-16EX-ES/UL FX0N-8EYR-ES/UL FX0N-8EYT-ESS/UL FX0N-16EYR-ES/UL FX0N-16EYT-ESS/UL FX0N-8ER-ES/UL Inputs 8 16 -- -- -- -- 4 Outputs -- -- 8 8 16 16 4 Output type -- -- Relay Transistor Relay Transistor Relay Module type FX2N-16EX-ES/UL FX2N-16EYR-ES/UL FX2N-16EYT-ESS/UL Inputs 16 -- --
FX0N FX2N
Outputs -- 16 16 Output type -- Relay Transistor
MITSUBISHI ELECTRIC
31
MELSEC FX0N/FX2N
EXTENSION UNITS Specifications
Compact Extension Units
FX0N FX2N
Extension Units FX0N
The FX0N series extension units are available with 40 input/output points. It is possible to choose between relay and transistor output type.
FX
BASICS
Special features:
LEDs for indicating the input and output status MELSEC FX2N series compatible Integrated service power supply with up to 200 mA capacity
Specifications Electrical data Integrated inputs/outputs AC range (+10%, -15%) Power Frequency at AC supply DC range (+20%, -15%) Max. input apparent power 100 V AC Inrush current at ON 200 V AC 24 V DC Allowable momentary power failure time Externalservice power supply (24 V DC) Inputs Integrated inputs Min. current for logical 1 Max. current for logical 0 Response time Outputs Integrated outputs Output type Max. switching voltage - per output Max. output current - per group* Max. switching - inductive load power - lamp load Response time Life of contacts (switching times) Mechanical data Weight Dimensions (W x H x D) Order information
FX0N-40 ER-ES/UL 40 AC 100 - 240 V Hz 50/60 (10%) -- 40VA 30 A / 5 ms 50 A / 5 ms -- ms 10 mA 200
FX0N-40 ER-DS 40 -- -- DC 24 V 20W -- -- 60 A / 50 s 10 --
FX0N-40 ET-DSS 40 -- -- DC 24 20 W -- -- 60 A / 50 s 10 -- 24 3.5 1.5
24 24 mA 3.5 3.5 mA 1.5 1.5 For all base units of the MELSEC FX0N series values:10 ms (at time of shipment)
A A VA W ms
16 16 16 Relay Relay Transistor Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 - 30 V DC 2 2 0.5 -- -- 0.8 80 80 12 100 100 1,5 10 10 < 0.2 For all extension units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA 0.6 150 x 90 x 87 55955 0.6 150 x 90 x 87 55954
kg 0.6 mm 150 x 90 x 87
Art. no. 60012
* Thislimitation applies only per reference terminal for eachgroup,4 and 8 outputsfor relaysand 2 and 4 outputsfor transistors.Please observetheterminal assignmentsfor the group identification.
32
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications EXTENSION UNITS
Compact Extension Units
FX0N FX2N
Extension Units FX2N
The FX2N series extension units are available with 32 or 48 input/output points. It is possible to choose between relay and transistor output type.
FX
BASICS
Special features:
LEDs for indicating the input and output status MELSEC FX0N series compatible Detachable terminal blocks Integrated service power supply with up to 200 mA or 460 mA
Specifications Electrical data Integrated inputs/outputs AC range (+10 %, -15 %) Power Frequency at AC supply DC range (+20 %, -30 %) Max. input apparent power 100 V AC Inrush current at ON 200 V AC Allowable momentary power failure time External service power supply (24 V DC) Power supply int. bus (5 V DC) Inputs Integrated inputs Min. current for logical 1 Max. current for logical 0 Response time Outputs Integrated outputs Output type ON voltage (max.) - per output Max. output current - per group* Max. switching - inductive load power - lamp load Response time Life of contacts (switching times) Mechanical data Weight Dimensions (W x H x D) Order information
FX2N-32 ER-ES/UL 32 100 - 240 V AC Hz 50/60 (10 %) -- 35VA 50 A < 5 ms 60 A < 5 ms ms 10 mA 250 mA 690
FX2N-32 ET-ESS/UL 32 100 - 240 V AC 50/60 (10 %) -- 35VA -- -- 10 250 690
FX2N-48 ER-DS 48 -- -- 24 V DC 30W 50 A < 5 ms 60 A < 5 ms 10 -- 690
FX2N-48 ER-ES/UL 48 100 - 240 V AC 50/60 (10 %) -- 45 VA 50 A < 5 ms 60 A < 5 ms 10 250 690
FX2N-48 ET-DSS 48 -- -- 24 V DC 30 W 50 A < 5 ms 60 A < 5 ms 10 -- 690 24 3.5 1.5
FX2N-48 ET-ESS/UL 48 100 - 240 V AC 50/60 (10 %) -- 45VA 50 A < 5 ms 60 A < 5 ms 10 460 690 24 3.5 1.5
16 16 24 24 mA 3.5 3.5 3.5 3.5 mA 1.5 1.5 1.5 1.5 For all extension units of the MELSEC FX2N series values:10 ms (at time of shipment)
16 16 24 24 24 Art Relay Transistor Relay Relay Transistor Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 - 30 V DC A2 0.5 2 2 0.5 A8 0.8 8 8 0.8 W 80 12 80 80 12 W 100 1.5 100 100 1.5 ms 10 < 0.2 10 10 < 0.2 For all extension units of the MELSEC FX2N series values:3000000 at 35 VA;1000000 at 80 VA;200000 at 120 VA kg 0.65 mm 150 x 90 x 87 0.65 150 x 90 x 87 65569 0.85 182 x 90 x 87 66633 0.85 182 x 90 x 87 65571 0.85 182 x 90 x 87 66634
24 Transistor 0.5 0.8 12 1.5 < 0.2
0.85 182 x 90 x 87 65572
Art. no. 65568
MITSUBISHI ELECTRIC
33
MELSEC FX0N/FX2N
EXTENSION UNITS Specifications
Modular Extension Units
FX0N FX2N
Extension Units FX0N
The FX0N series modular extension units are available with 8 or 16 input/output points. It is possible to choose between relay and transistor output type.
FX
BASICS
Special features:
IN
LEDs for indicating the input and output status MELSEC FX2N series compatible Vertically mounted (at 8 I/Os) or horizontally mounted (at 16 I/Os) terminal blocks with a cable guide to the upper or lower side
Specifications Electrical data Integrated inputs/outputs Power supply Inputs Integrated inputs Min. current for logical 1 Max. current for logical 0 Response time Outputs Integrated outputs Output type Max. switching voltage - per output Max. output current - per group* Max. switching - inductive load power - lamp load Response time Life of contacts (switching times) Mechanical data Weight Dimensions (W x H x D) Order information
FX0N-8 ER-ES/UL
FX0N-8 EX-ES/UL
FX0N-8 EYR-ES/UL
FX0N-8 EYT-ESS/UL 8
FX0N-16 EX-ES/UL 16
FX0N-16 EYR-ES/UL 16
FX0N-16 EYT-ESS/UL 16
8 8 8 All modulare extension units are supplied by the base unit. 4 8 -- mA 3.5 3.5 -- mA 1.5 1.5 -- For all extension units of the MELSEC FX0N series values:10 ms
-- -- --
16 3.5 1.5
-- -- --
-- -- --
A A VA W ms
4 -- 8 8 -- Relay -- Relay Transistor -- Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 - 30 V DC 2 -- 2 0.5 -- -- -- -- 0.8 -- 80 -- 80 12 -- 100 -- 100 1.5 -- 10 10 10 < 0.2 10 For all extension units of the MELSEC FX0N series values:3000000 at 20 VA;1000000 at 35 VA;200000 at 80 VA 0.2 43 x 90 x 87 60013 0.2 43 x 90 x 87 60014 0.2 43 x 90 x 87 60016 0.3 70 x 90 x 87 55952
16 Relay 2 -- 80 100 10
16 Transistor 0.5 0.8 12 1.5 < 0.2
kg 0.2 mm 43 x 90 x 87 Art. no. 60023
0.3 70 x 90 x 87 55951
0.3 70 x 90 x 87 55950
* Thislimitation applies only per reference terminalfor eachgroup,4 and8 outputs for relaysand 2 and 4 outputsfor transistors.Please observe the terminal assignments for thegroup identification.
34
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Specifications EXTENSION UNITS
Modular Extension Units
FX0N FX2N
Extension Units FX2N
The FX2N series modular extension units are available with 16 input/output points. It is possible to choose between relay and transistor output type.
FX
BASICS
OUT
Special features:
LEDs for indicating the input and output status MELSEC FX0N series compatible Especially compact design Vertical mounted terminal blocks with a cable guide to the upper or lower side
OUT
Specifications Electrical data Integrated inputs/Outputs Power supply Inputs Integrated inputs Min. current for logical 1 Max. current for logical 0 Response time Outputs Integrated outputs Output type ON voltage (max.) - per output Max. output current - per group* Max. switching - inductive load power - lamp load Response time Life of contacts (switching times) Mechanical data Weight Dimensions (W x H x D) Order information
FX2N-16 EX-ES/UL
FX2N-16 EYR-ES/UL
FX2N-16 EYT-ES/UL 16
16 16 All modulare extension units are supplied by the base unit. 16 -- mA 3,5 -- mA 1,5 -- For all base units of the MELSEC FX2N series values:10 ms (at time of shipment) -- 16 -- Relay Generally for relay version:< 264 V AC,< 30 V DC;for transistor version:5 - 30 V DC -- 2 -- -- -- 80 -- 100 -- 10 -- Same as base unit 0,3 40 x 90 x 87 65580
-- -- --
16 Transistor 0,5 0,8 12 1,5 < 0,2 -- 0,3 40 x 90 x 87 65581
V A A VA W ms
kg 0,3 mm 40x90x87 Art. no. 65776
* Thislimitation applies only per reference terminalfor each group,4 and 8 outputsfor relays and2 and4 outputs for transistors.Pleaseobservetheterminal assignmentsfor the group identification.
MITSUBISHI ELECTRIC
35
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Analog Modules FX0N FX2N
PLC program using the dedicated instructions VRRD/VRSC (FNC85/86). The FX2N-8AV-BD adapter board is installed in the expansion slot of the FX2N CPU. No additional power supply is required for operation.
Analog Setpoint Adapter FX2N-8AV-BD
FX
BASICS
The FX2N-8AV-BD enables the user to set 8 analog setpoint values. The analog values of the potentiometers are read into the controller and used as default setpoint values for timers, counters and data registers by the user's PLC programs. Setpoint value polling and the definition of the potentiometer scales are performed in the
Specifications General specifications Power supply Adjusting range Related I/O points Potentiometer evaluation Weight Dimensions (W x H) Order information kg mm Art. no.
FX2N-8AV-BD Conforms to base units From base unit 8 bit 0 Via application instruction from the PLC CPU (FNC 85/86) 0.08 52 x 35 65594
JY331B88801B
Analog Module FX0N-3A
The analog module FX0N-3A provides the user with 2 analog inputs and 1 analog output. They serve for conversion of analog process signals into digital values, and vice versa.
FX0N FX2N
The analog module is connected to the base unit via a protected flat cable. The connection is to the extension bus on the right side of the controller.
Specifications General specifications Dielectric withstand voltage Power supply Number of analog points Analog data I/O resolution Total accuracy Conversion time Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no. AD/DA ms inputs outputs voltage current V DC mA
FX0N-3A Conforms to base units 500 V AC for 1 minute 24 V DC / 90 mA (from base unit),5 V DC / 30 mA 2 1 0 - 10 / 0 - 5 DC 4 - 20 20 mV/ 64 A (8 bit) 1 % 0.1/point 8 0.2 43 x 90 x 87 41790
36
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Analog Modules SPECIAL FUNCTION MODULES FX0N FX2N
CPU vers. 2.00
Analog Output Module FX2N-4DA
These analog output modules provide the user with 4 analog outputs. The modules convert digital values from the FX0N/FX2Ncontroller to the analog signals required by the process.
24+ VII+ V+ VII+ V+ 24-
The modules can output both current and voltage signals.
FX
BASICS
Specifications General specifications Power supply Analog channels
FX2N-4DA
FX2N-4DA Conforms to base units 5 V DC/ 30mA(frombaseunit),24V DC/200mA -- 4 -10 V DC - +10 V DC / 0 mA - +20 mA voltage output current output voltage current V mA 2 k - 1 M < 500 10 0 - 20 5 mV / 20 A (11 bit + sign) 1 % analog digital digital analog ms ms kg mm Art. no. -- 2.1 for 4 channels 8 0.3 55 x 90 x 87 65586
V+
inputs outputs
Analog Input Module FX2N-4AD
The analog input module FX2N-4AD provides the user with 4 analog inputs. The module converts analog process signals into digital values which are further processed by the MELSEC FX0N/FX2N controller.
24+ VII+ FG V+ VII+ FG V+ VII+ FG V+ VI24V+
MITSUBISHI ELECTRIC
VII+
Analog output range
24+ 24-
V+ VII+
I+
External load Analogdata Resolution Overall accuracy Conversion speed Related I/O points Weight Dimensions (W x H x D) Order information
FX2N-4DA
V+ VII+ V+ VI-
FX 2N-4DA
I+ V+
I+ V+
VIVI24+ VIFG VIFG VIFG VI-
I+
24V+ I+ V+ I+ V+ I+ V+ I+
D/A
FX0N FX2N
CPU vers. 2.00
The actual values or mean values over several measurements may be output.
Specifications General specifications Power supply Analog points Analog input range Input resistance Analog data Resolution Overall accuracy Conversion speed Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no. analog digital digital analog ms voltage input current input voltage current k V mA inputs outputs
FX2N-4AD Conforms to FX2N base units 5 V DC / 30 mA (from base unit),24 V DC / 50 mA 4 -- -10 V DC - +10 V DC / -20 mA - +20 mA / 4 - 20 mA 200 250 10 20 5 mV / 20 A (11 bit + sign) 1 % 15perchannel/60per4channels (high-speed) -- 8 0.3 55 x 90 x 87 65585
37
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Analog Modules FX0N FX2N
CPU vers. 2.00
Analog Input Module for Thermo Elements FX2N-4AD-TC
FX
BASICS
This special function module FX2N-4AD-TC is used for processing temperatures. It has 4 independent inputs for detecting signals from thermocouples of types J and K. The type of thermocouple can be chosen independently for each point. The electrical magnitude at an input is converted into a digital numerical value with a sign. The converted value is stored by the PLC in a memory address, so-called buffer memory, in the module and then converted. It is also possible to calculate
FX2N-4AD-TC
a mean value from a predetermined number of measurements in order to obtain stable digital results. The number of measurements must be transferred by the PLC program to a buffer memory of the special function module. The value determined is available in another memory address.
Analog Input Module for Pt100 Inputs FX2N-4AD-PT
The analog input module FX2N-4AD-PT permits the connection of four Pt100 sensors to the FX controller.
24+ L+ LFG IL+ LFG IL+ FG IL+ L24I-
24+ L+ L+ L+ L+
24- SLD LSLD LSLD LSLD LL-
24+ L+ L+ L+ L+
FX 2N-4AD-TC
FX2N-4AD-TC
LSLD L-
24- SLD LSLD LSLD
Specifications General specifications Power supply Analog inputs Compensated temperature range Digital output Resolution Overall accuracy Conversion speed Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no. ms C C
FX2N-4AD-TC Conforms to FX2N base units 5 V DC / 30 mA (from base unit),24 V DC / 50 mA 4 (K or J type) -100 - +600 (J type) / -100 - +1200 (K type) -1000 - +6000 (J type) / -1000 - +12000 (K type) 0.3 (J type) / 0.4 (K type) 0.5 % 240 per channel (2 %) 8 0.3 55 x 90 x 87 65588
FX0N FX2N
CPU vers. 2.00
The respective temperatures can be read out either in C or F.
Specifications General specifications Power supply Analog inputs Compensated temperature range
24+
FX2N-4AD-PT Conforms to FX2N base units 5 V DC / 30 mA (from base unit),24 V DC / 50 mA 4 (Pt100 sensors) C C -100 - +600 -1000 - 6000 (12 bit conversion) 0.2 1 % over full linear range ms 15 for 4 channels 8 kg mm Art. no. 0.3 55 x 90 x 87 65587
FX2N-4AD-PT
Digital output Resolution Overall accuracy Conversion speed Related I/O points Weight Dimensions (W x H x D) Order information
FX2N-4AD-TC
24- SLD LSLD
L+ L+ L+ L+ L-
FX 2N-4AD-PT
LSLD
LSLD
38
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
High-Speed Counter and Positioning Module SPECIAL FUNCTION MODULES FX0N FX2N
CPU vers. 2.00
High-Speed Counter FX2N-1HC
In addition to the internal high-speed MELSEC FX counters, the high-speed counter module FX2N-1HC provides the user with an external hardware counter. It counts 1- or 2-phase pulses up to a frequency of 50 kHz. The counting range covers either 16 or 32 bit.
The two integrated transistor outputs can be switched independently of one another by means of internal comparison functions. Hence, simple positioning tasks can also be realized economically. In addition, the FX2N-1HC can be used as a ring counter.
FX
BASICS
Specifications General specifications Signal level Power supply Counter inputs Max. counting frequency Input format Typ of counter Conting range Output type Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no. 16 Bit 32 Bit
FX2N-1HC Conforms to FX2N base units 5,12,24 V DC / 7 mA 5 V DC / 90 mA from base unit 2 (1 phase) oder 1 (2 phase) 50 16,32 Up/down counter,ring counter -2147483648 - +2147483647 0 - 65535 2 x transistor (5 - 24 V DC;0.5 A) 8 0.3 55 x 90 x 87 65584
kHz Bit
Single Axes Positioning Module FX2N-1PG-E
The positioning module FX2N-1PG-E is an extremely efficient single-axis positioning module for controlling either step drives or servo drives (by external regulator) with a pulse chain. It is very suitable for achieving accurate positioning in combination with the MELSEC FX series. The configuration and allocation of the position data are carried out directly via the PLC program. A very wide range of manual and automatic functions are available to the user.
FX0N FX2N
CPU vers. 2.00
1PG
POWER
Further special features are: Possibility of absolute or relative positioning 7 different operation functions, such as jog mode, zeroing, variable speeds, etc. Separate programming units and operator panels are not required. The speed increase or decrease can be set either automatically or manually.
MITSUBISHI ELECTRIC
RP PG0+ CLR STOP DOG COM1 S/S S/S
Specifications
FX 2N -1PG
POWER
S TDP OOG PGO
FX2N-1PG-E Conforms to FX2N base units 24 V DC / 7-40 mA 5 - 24 V DC / 60 mA 1 pulse/s 10 - 100 000 8 kg mm Art. no. 0.3 43 x 90 x 87 65583
FRCE PPLR RR
General specifications Signal level for digital inputs Power supply Accessible axes Output frequency Related I/O points Weight Dimensions (W x H x D) Order information
39
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Interface Modules FX0N FX2N
CPU vers. 2.00
Active Data Interface FX0N-232ADP
FX
BASICS
The additional RS232C interface FX0N232ADP permits active communication between the PLC and surrounding RS232C peripherals. All operands can be sent or received via this interface. Devices can be transmitted via this interface. A program transfer or the connection of an MAC terminal is not possible.
The module is suitable for the connection of printers, bar code readers, PCs and other PLC systems. The communication is handled by the PLC program using the RS instruction. The connection is to the communications bus on the left side of the controller. The internal serial RS422 interface is also fully available.
Specifications General specifications Interface Power supply Communication speed Communication distance Communication cable Communication mode Protocols Format Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no.
FX0N-232ADP Conforms to FX0N/FX2N base units RS232with25poleD-SUBcompactplug(photocouplerisolated) 5 V DC / 200 mA (from base unit) 300,600,1200,2400,4800,9600,19200 Max.15 Shielded cable Half duplex Non-protocolmode/freeprogrammableviaPLC 7 or 8 bits,parity 1 or 0,1 or 2 stop bit -- 0.2 43 x 90 x 68 42211
Bit/s m
Interface Module FX2N-232IF
The FX2N-232IF module provides an RS-232C interface for serial data communications with the MELSEC FX2N/FX0N. Communication with PCs, printers, modems, barcode readers etc. is handled by the PLC program using FROM/TO instructions.
Specifications General specifications Interface Power supply Communication speed Communication distance Communication cable Communication mode Protocols Format Send and receive buffer Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no.
FX0N FX2N
CPU-Vers. 2.00
The send and receive data are stored in the FX2N-232IF's own buffer memory. Changes at the user program are not possible via this interface.
FX2N-232IF Conforms to FX2N base units RS232 with 9 pole D-SUBconnector (photocouppler isolation) 5 V DC / 40 mA (from base unit),24 V DC / 80 mA 300,600,1200,2400,4800,9600,19200 Max.15 Shielded cable Full duplex Nonprotocolmode/startstopsynchronisation 7 or 8 data bits,parity 1 or 0,1 or 2 stop bit 512 byte each 8 0.3 55 x 90 x 85 66640
bit/s m
40
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Interface Modules SPECIAL FUNCTION MODULES FX0N FX2N
The FX2N-232BD interface adapter board provides an RS-232C interface for serial data communications with the MELSEC FX2N. Data and programmes can be transferred with the standard RS-232 protocol. The unit's integrated automatic parameter setting facility also makes it possible to configure a modem - for example for remote programming and maintenance tasks. Data can be transferred directly to other serial peripherals using the RS dedicated instruction. Connected programming systems are identified automatically. The adapter board is installed in the expansion slot provided for it in the FX2N base unit. If the adapter is used no other adapters can be used. If additional RS232C interfaces are required, the FX2N-232IF can be used for extension.
Interface Adapter FX2N-232BD
FX
BASICS
Specifications General specifications Interface Power supply Communication speed Communication distance Communication mode Protocols Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no.
FX2N-232-BD JY331B89001C
FX2N-232BD Conforms to FX2N base units RS232 with 9 pole D-SUB connector 5 V DC / 60 mA (from base unit) 300,600,1200,2400,4800,9600,19200 Max.15 Half duplex Free programmable via PLC/ non-protocol mode / protocol 1 or 4 -- 0,08 35 x 54 x 22 65596
bit/s m
Interface Adapter FX2N-422BD
The FX2N-422BD interface adapter board provides a second RS-422 interface for connection of an additional device to the controller (programming unit or operator terminal). In addition to programming the PLC the main applications for this interface include production data logging, process visualisation and man-machine communication. If one programming unit is already connected to the integrated RS-422 interface it
FX0N FX2N
is not possible to connect a second one to the FX2N-422BD interface adapter. It is possible to connect two control units, however. The adapter is installed in the expansion slot provided for it in the FX2N base unit. No additional adapter boards can be used when this unit is installed.
FX2N-422-BD
JY331B89101B
Specifications General specifications Interface Power supply Communication distance Communication mode Protocols Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no. m
FX2N-422BD Conforms to FX2N base units RS422 8 pole mini DIN connector 5 V DC / 60 mA (from base unit) Max.50 Half duplex FreeprogrammableviaPLC -- 0.08 35 x 54 x 22 65595
MITSUBISHI ELECTRIC
41
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules
The MELSECNET/MINI Network
FX
BASICS
Data communications
MELSECNET/MINI enables fast data exchange with a variety of devices. Equipment you can integrate in this network type includes: Remote digital I/Os Analog I/Os High-speed counters Remote intelligence modules (e.g FX0N/FX2N) Frequency inverters (FR-A 540) Third-party equipment, e.g. FESTO/SMC
AnS/QnAS
Remote I/O
MELSECNET/MINI
Structure
The network's ring topology enables a very large maximum coverage: Max. 1700 m with shielded twistedpair cabling Max. 10000 m with shielded twistedpair cabling combined with fibreoptics cables
FX2N/FX0N with PPN network FX2N Frequency inverter
Cable types
The network supports a variety of different cable types as communications media: Shielded twisted-pair Acrylic fibre-optics cable (max. 50 m/ segment) Glass fibre-optics cable SI200/250 m (max. 1000 m/segment) Glass fibre-optics cable GI50/125 m (max. 2000 m/segment)
Specifications Cable type Communications rate distance between 2 stations total coverage internal resistance (at 20 C) electrostatic capacity impedance(100kHz) transmissionlosses inner/outer diameter
Electrical Shielded twisted-pair MBit/s 1.5 m 100 m 1700 88 / km nF 60 / km 110 (10) -- m -- RG59 Art. no.
Optical Acrylic fibre optic 1.5 50 850 -- -- -- 260 dB / km 980 / 1000 Glass fibre SI type 1.5 1000 6000 -- -- -- 12 dB / km 200 / 250 Glass fibre GI type 1.5 2000 10000 -- -- -- 3 dB / km 50 / 125
Media
Data exchange
This network can transport a variety of different data without any problems, including both digital and analog data. An FX0N/FX2N controller configured as a slave can exchange (transmit and receive) up to 28 data words with the master PLC (AnS, QnAS).
Connectors Connection system Order information
CA9104AP 17530
CA9003 9546
CA9003S 29603
Recommended shielded twisted-pair cabling (2 pairs): Lappkabel Unitronic Li2YCY (TP) paired (up to 100 m) or Unitronic Li2YCY (TP) finely-stranded (up to 50 m)
Administration
The programming software packages MELSEC MEDOC plus and MELSEC MINI-P make installation and set-up simple and trouble-free.
42
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Communications Modules SPECIAL FUNCTION MODULES FX0N FX2N
Thus the network is expandable via the digital inputs/outputs of the FX modules to a maximum of 512 I/Os. The connection is to the extension bus on the right side of the controller.
Communications Module FX0N-16NT
The communications module FX0N-16NT enables the user to connect to the MELSECNET/MINI with a superior A system as master CPU. This gives him access to the network of all MELSEC PLC systems and frequency inverters and to additional products from other suppliers.
FX
BASICS
Specifications General specifications Dielectric withstand voltage Power supply Communication speed Communication distance Communication cable Communication mode Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no.
FX0N-16NT Conforms to FX0N base units 500 V AC for one minute 24 V DC / 60 mA (from external power module) 1.5 50 at 0.2 - 0.5 mm2 100 at > 0.5 mm2 Shielded twisted pair 0.5 mm2 Bit transformation 16 0.2 43 x 90 x 87 41819
Mbit/s m
MITSUBISHI ELECTRIC
43
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules FX0N FX2N
CPU-Vers. 2.00
Communications Modules for MELSECNET/MINI FX-16NP and FX-16NT
FX
BASICS
These communications modules permit the linking of programmable logic controllers of the MELSEC FX0N/FX2N series as a local station in the MELSECNET/MINI with a superior A system as master CPU.
Specifications General specifications Power supply Master module Communications modules within network Data words Transformed bits Related I/O points I/O refresh time Communication speed Communication cable Communication distance Weight Dimensions (W x H x D) Order information m kg mm Art. no. ms MBit/s
For the connection of these modules to the FX0N or FX2N series the adapter FX2N-CNV-IF is needed.
FX-16NP
FX-16NT
Conforms to FX base units 5 V DC / 80 mA (from base unit),24 V DC / 120 mA AJ71PT32-S3 A(1S)J71PT32-S3 or A2CCPU Max.32 -- 8 sent / 8 received 24 3-4 1.5 Plastic fibre 50 0.3 45 x 140 x 95 25196 Max.32 -- 8 sent / 8 received 24 3-4 1.5 Twisted pair 50 (at 0.2-0.5mm2) 100 (at 0.5 mm2) 0.3 45 x 140 x 95 25197
Communications Modules for MELSECNET/MINI FX-16NP-S3 and FX-16NT-S3
These communications modules permitthe linking of programmable logic controllers of the MELSEC FX0N-/FX2N series as a local station in the MELSECNET/MINI-S3 with a superior A system as master CPU. In a S3 network, in addition to data exchange via digital inputs and outputs, it is also possible to transfer data words (max. 56), with the result that, for example,
Specifications General specifications Power supply Master station Communications modules within network Data words Transformed bits Related I/O points I/O refresh time Communication speed Communication cable Communicatin distance Weight Dimensions (W x H x D) Order information m kg mm Art. no. ms MBit/s
FX0N FX2N
CPU-Vers. 2.00
processing of analog values in the network with the FX0N-/FX2N series is possible. Max. 16 of these communications modules can be integrated in a MELSECNET/MINI-S3. For the connection of these module to the FX0N or FX2N series the adapter FX2N-CNV-IF is needed.
FX-16NP-S3
FX-16NT-S3
Conforms to FX base units 5 V DC / 80 mA (from base unit),24 V DC / 100 mA AJ71PT32-S3 A(1S)J71PT32-S3 or A2CCPU Max.16 FX A:28 / A FX:28 8 sent / 8 received 24 3-4 1.5 Plastic fibre 50 0.4 73 x 140 x 95 33714 Max.16 FX A:28 / A FX:28 8 sent / 8 received 24 3-4 1.5 Twisted pair 50 (at 0.2-0,5mm2) 100 (at 0.5 mm2) 0.4 73 x 140 x 95 33715
44
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Communications Modules SPECIAL FUNCTION MODULES
MELSEC Peer-to-Peer Network, 1:n Network, Parallel Link
The networks in details:
Peer-to-Peer You can integrate up to 8 programmable logic controllers in a peer-to-peer network. All stations in the network can monitor all the devices in the entire data range. However, data writing and setting and resetting of individual devices is always only performed in the specific station in question. Each network station can transfer packets of up to 64 bits and 8 data words via the network. The maximum distance between the first and last connected stations depends on the type of adapters used: FX0N-485ADP: max. 500 m (CPU vers. 2.0) FX2N-485BD: max. 50 m
FX
BASICS
Master station
485BD/ 485ADP
FX2N
Slave
Slave
Slave
485BD/ 485ADP
FX0N/FX2N
485BD/ 485ADP
FX0N/FX2N
485BD/ 485ADP
FX0N/FX2N
RS485 nezwork
1 : n Multidrop-Netzwerk This network is used for displaying and monitoring data from the individual stations on a connected computer. You can connect up to 16 stations in one of these networks. The maximum distance between the first and last connected station depends on the type of adapters used: FX0N-485ADP: max. 500 m FX2N-485BD: max. 50 m
Personal computer with FX-485PC-IF
AnA / AnU / QnA
Interface unit
FX0N / FX2N
FX0N / FX2N
FX0N / FX2N
Parallel Link As the name indicates, parallel link mode connects two programmable logic controllers with a parallel link. Data communication between the two states is performed automatically via a predefined range of relays and data registers. The maximum distance between two stations connected by parallel link is 50 m. If the FX0N-485 ADP is used, the maximum distance will be 500 m.
Master station
FX2N
FX2N
MITSUBISHI ELECTRIC
45
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules FX0N FX2N
The FX2N-485BD interface adapter board provides the FX2N unit with an additional RS-485 interface. The adapter, which is simply inserted into the base unit's expansion slot, enables the configuration of RS-485 1:n multidrop, parallel link or peer-to-peer networks with FX0N/FX2N systems. You can also transfer data directly to other RS-485 peripherals using the RS dedicated instruction. In peer-to-peer network configurations the adapter enables active communication between the individual FX0N/FX2N controllers via the RS-485 interfaces. In 1:n multidrop networks the adapter can be use to provide communication with a host master station of the A series.
Interface Adapter FX2N-485BD
FX
BASICS
Communications Module FX0N-485ADP
The FX0N-485ADP communications module enables the configuration of 1:n multidrop, parallel link and peer-to-peer data networks using the RS-485 interface. Configuration of peer-to-peer data networks requires version 2.00 of the FX0N485ADP (see p. 21 for details).
RDA RDB SDA SDB SG
Specifications
FX2N-485-BD JY331B88901C
FX2N-485BD Conforms to FX2N base units 5 V DC / 60 mA from base unit RS485 / RS422 300 - 19200 Twisted pair m max.50 Protocol 1 or 4 of AJ71UC24 /noprotocol/parallellink/ peer-to-peernetwork Station kg mm Art. no. 0 0.08 35 x 54 x 22 65597
General specifications Power supply Interface Communication speed Communication cable Communication distance Protocols Related I/O points Weight Dimensions (W x H x D) Order information
bit/s
FX0N FX2N
In FX0N systems the module is connected directly to the communications bus on the left-hand side of the FX0N base unit. The FX2N-CNV-BD communications adapter is required for connection to FX2N base unit.
Specifications General specifications Power supply Interface Communication speed Communication distance Communication cable Communication mode Protocols Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no.
FX0N-485ADP Conforms to FX0N base units 5 V DC / max.30 mA (from base unit),24 V DC / 50 mA RS485 300 - 19200 Max.500 Shielded cable Half duplex Protocol1and4ofAJ71UC24 -- 0.3 43 x 90 x 87 66665
bit/s m
46
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Communications Modules SPECIAL FUNCTION MODULES FX0N FX2N
Interface Unit for RS485 1:n Multidrop Network FX-485PC-IF
The interface unit FX-485PC-IF is used for converting interface signals. The module has an RS232C interface for connection to a PC and RS485 ports for connection to the network.
FX
BASICS
Specifications General specifications Current consumption Power supply Interface Communication speed Communication cable Communication distance Communication mode Protocols Weight Dimensions (W x H x D) Order information kg mm Art. no. m mA
FX-485PC-IF Conforms to FX2N base units 260 5 V DC 5 % RS232 / RS485 300,600,1200,2400,4800,9600,19200 Shielded cable 15 (RS232) 500 (RS485) Half duplex Protocol 1 and 4 of AJ71UC24 0.3 100 x 80 x 30 53416
bit/s
The power supply is used for the interface unit FX-485PC-IF.
Specifications General specifications Power supply Weight Dimensions (W x H x D) Order information kg mm Art. no.
SC06 N-PG Conforms to FX2N base units 5 V DC / 800 mA
32630
MITSUBISHI ELECTRIC
47
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules
The PROFIBUS/DP Network
FX
BASICS
Data Communications
The open PROFIBUS/DP network enables extremely fast data exchange with a very wide variety of slave devices, including: Remote digital I/Os Remote intelligence PLC (FX0N, FX2N) Frequency inverters (FR-A 024/044, FR-A 240 and MELTRAC 140) Operator terminals (MAC) A range of other devices from thirdparty manufacturers
Master PLC
AnS / QnAS
AnA / AnU / QnA
Slave units
max. 1.200 m at 93.75 kBit/s without repeater
FX0N / FX2N
Structure
The maximum coverage of a bus segment is 1200 m (at a maximum of 93.75 kbit/s). Up to 3 repeaters are allowed. Thus the maximum distance between 2 stations is calculated with 4800 m.
E300/E700
PROF
PROCESS FIELD BUS
I
BUS
Cable types
To help reduce costs PROFIBUS/DP uses RS-485 technology with simple twistedpair cabling. Suitable cables include the UNITRONIC BUSLD from Lappkabel and the DUE 4451 from Alcatel.
FR-A 024/044 FR-A 240/540 MELTRAC
16 outputs
Specifications Communications protocol Cabling
Master AJ71PB92
Master A1SJ71PB92D
Data exchange
The PROFIBUS AJ71PB92 and A1SJ71PB92D master modules support slave device data exchange with up to 32 send bytes and 32 receive bytes. This means you can exchange a total of up to 64 bytes with a slave unit per network cycle.
Interface distance 1 200 m 1 000 m 400 m 200 m Max total distance Slave units per master Stations per segment Repeaters per network
EN 50170 / DIN 19245-T3 Shielded twisted-pair with 24 AWG = 0,22 mm2,impedance:100 - 130 ; Shielded twisted-pair with 22 AWG = 0,34 mm2,impedance:135 - 165 ; RS485 kbit/s 9.6 / 19.2 / 93.75 kbit/s 187.5 kbit/s 500 kbit/s 1 500 m 4800 (3 repeaters) 60 32 3 ProfiCon:PROFIBUS 9-pin D-SUB plug connector for up to 12 Mbaud, art.no.64127 or art. 87035 (see page 73) ; ProfiMap:configurations software for MELSEC master modules and third party devices, art.no.102996 (see page 71) 12000 / 6000 / 3000 (100 m) 1500 (200 m)
Data transfer rate
Administration
In combination with the MELSEC ProfiMap configuration software the A1SJ71PB92D PROFIBUS/DP master unit gives you user-friendly plug-and-play technology. The configuration software is self-explanatory, using a graphical model for setting up the network. You simply select the slave unit (e.g. FX2N), assign the station numbers and specify where the information is stored in the Master CPU. Of course, PROFIBUS/DP slaves from MITSUBISHI ELECTRIC can also be connected to master devices from other manufacturers.
Accessories
48
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Communications Modules SPECIAL FUNCTION MODULES FX0N FX2N
It links the system to the master PLC in the Profibus DP network for efficient and trouble-free data exchange.
Profibus DP Slave Module FX0N-32NT-DP
The FX0N-32NT-DP Profibus module enables you to integrate a MELSEC FX0N/FX2N system in an existing Profibus DP network. This interface module provides your FX0N or FX2N CPU with an intelligent Profibus DP link for the implementation of decentralised control tasks.
24G 24+ FG
FX
BASICS
FXON-32NT -DT
Specifications General specifications Power supply Interface distance 1200 m Communication speed 1000 m 200 m 100 m Communication distance Communication cable Related I/O points Weight Dimensions (W x H x D) Order information kg mm Art. no. kbit/s kbit/s kbit/s kbit/s m
FX0N-32NT-DP Conforms to FX0N base units 5 V DC / max.170 mA (from base unit),24 V DC / 60 mA Profibus DP 9.6 / 19.2 / 93.75 187.5 1500 3000 / 6000 / 12000 Max.1200 (dependson communicationspeed) PROFIBUS cable with 9-pin D-SUB plug 8 0.3 43 x 90 x 87 62125
FX 0N -32NT-DP
POWER DC RUN
BF
DIA
MITSUBISHI ELECTRIC
49
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES Communications Modules FX0N FX2N
tal FX modules and special function modules.
Communications Adapter FX2N-CNV-IF
FX
BASICS
MITSUBISHI
The FX2N-CNV-IF communications adapter (IF = interface) enables you to connect your FX series special function modules to FX0N/FX2N systems. The adapter provides compatibility between the FX0N/FX2N CPU and the digiSpecifications General specifications Power supply Related I/O points Weight Dimensions (W x H x D) kg mm Art. no.
FX2N-CNV-IF Conforms to FX2N base units Not necessary 0 0.15 23 x 140 x 45 65599
FX2N-CNV-IF
Order information
Communications Adapter FX2N-CNV-BD
The FX2N-CNV-BD communications adapter (BD = function board) enables connection of the FX0N-232ADP and FX0N-
FX0N FX2N
485ADP special function modules to the left-hand side of the FX2N base units.
Specifications
FX2N-CNV-BD JY331B89201B
FX2N-CNV-BD Conforms to FX2N base units Not necessary 0 kg mm Art. no. 0.08 54 x 35 65598
General specifications Power supply Related I/O points Weight Dimensions (W x H) Order information
50
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
SPECIAL FUNCTION MODULES
FX
BASICS
MITSUBISHI ELECTRIC
51
MELSEC FX0N/FX2N
ACCESSORIES Memory Cassettes - Interface Converter FX0N FX2N
program specified in the respective memory cassette is run. The program contained in the internal memory is retained due to battery buffering.
Memory/Real-Time Clock Cassettes
FX
BASICS
All FX0N/FX2N base units are equipped with a slot for the optional, robust FX memory cassettes. By connection of these cassettes, the internal memory of the controller is switched off and only the
Data Memory type Size Accessory Order information
FX-RAM-8 RAM 16000 steps (FX2N) -- Art. no. 23823
FX-EPROM-8 EPROM 8000 steps -- 23824
FX-EEPROM-4 EEPROM 4000 steps -- 23825
Data Memory type Size Accessory Order information
FX-EEPROM-4C EEPROM 4000 steps Real-time clock Art. no. 23833
FX-EEPROM-8 EEPROM 8000 steps -- 23826
FX-EEPROM-16 EEPROM 16000 steps -- 65600
FX-RTC Real-time clock -- Battery (optional) 23831
Interface Converter CR01-R2/R4 SET and CR01-R4/R4
This module is a signal amplifier with photocoupler isolation for RS422 signals. It is used to connect a PLC with external devices like operation panels or a personal
FX0N FX2N
computer, especially when a potential isolation is required and when the wiring length takes more than 15 meters.
Specifications
Interface convertation
CR01-R4/R4 RS422 RS422 Art. no. 56173
CR01-R2/R4 SET RS422 RS232 (with SC09) 56172
Order information
52
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
PROM Adapter - Simulation Strip - Switch Box ACCESSORIES
PROM Adapter FX-ROM SOC1
The PROM adapter is used for adapting memory cassettes to a Textool base. This socket is required if the memory cassette EPROM-8 is to be written with a commercial EPROM loader in order, for example, to load a MEDOC program.
FX
BASICS
Data Order information
FX-ROM SOC1 Art. no. 27163
Simulation Strip: Input-SIM
The simulation strip has 8 switches for simulating digital inputs. The strip is directly mounted to the terminals of the unit and fixed with screws to the terminal block. A cable is provided for connecting the strip to the power supply. Two different simulation strips are available due to the differences within the terminal block between the MELSEC FX0N and FX2N series PLC. The simulation strip can be expanded with another strip for further inputs.
24V 0V
24V 0V
Input-SIM: FXOS/FXON
1
3
5
7
0
2
4
6
X00
-
X07
Data Switches Application Dimensions(WxHxD) Order information
Input-SIM: FX0S/FX0N 8 FX0S and FX0N series mm 30 x 50 x 15 Art. no. 65081
Input-SIM: FX2N 8 FX2N series 30 x 50 x 15 66513
Switch Box
The simulation box has 12 switches for simulating digital inputs. It can be used on all controllers of the MELSEC FX familiy.
Data Switches Order information
Switch-Box 12 Art. no. 3386
MITSUBISHI ELECTRIC
53
MELSEC FX0N/FX2N
ACCESSORIES Batteries FX0N FX2N
The battery F2-40BL can be used for all units of the MELSEC FX2N series. The battery buffers the internal RAM of the MELSEC FX2N PLC in the event of a voltage failure.
Battery F2-40BL2N
FX
BASICS
Data Order information
F2-40BL Art. no. 5142
Battery FX0N-40B
The battery FX0N-40B can be used for all units of the MELSEC FX0N series if these units are provided with a real-time clock cassette.
FX0N FX2N
The battery buffers the internal real-time clock.
Data Order information
FX0N-40B Art. no. 44331
54
MITSUBISHI ELECTRIC
MELSEC FX0N/FX2N
Connection Cable ACCESSORIES
Connection Cable for Base and Compact Extension Units
The cable is used for connection between a base unit or and a compact extension unit. This permits a multi-row arrangement of a MELSEC FX0N-/FX2N-System. The cable must be connected to the left side of the compact extension unit.
FX
BASICS
Data Type Length Order information
FX0N-65EC Flat cable m 0.65 Art. no. 45348
MITSUBISHI ELECTRIC
55
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment
Base Units MELSEC FX0N
FX
BASICS
FX0N-24MT-DSS
+
S/S X0 S/S X0 S/S
X1 X2 X1 X2 X1 X0 X2
X3 X4 X3 X4 X3 X4
X5 X6 X5 X6 X5 X6
X7
X11 X13 X15 X10 X12 X14 X11 X13 X15 X10 X12 X14 X11 X13 X15 X10 X12 X14
FX0N-40MT-DSS
+
S/S
S/S X0
X1 X2 X1 X0 X2 X1 X0 X2
X3 X4 X3 X4 X3 X4
X5 X6 X5 X6 X5 X6
X7
X11 X13 X15 X17 X21 X23 X25 X27 X10 X12 X14 X16 X20 X22 X24 X26 X11 X13 X15 X17 X21 X23 X25 X27 X10 X12 X14 X16 X20 X22 X24 X26 X11 X13 X15 X17 X21 X23 X25 X27 X10 X12 X14 X16 X20 X22 X24 X26
FX0N-24MR-DS
+
X7
FX0N-40MR-DS
+
S/S
S/S
X7
FX0N-24MR-ES/UL
X7
L
N
FX0N-40MR-ES/UL
S/S L N
S/S
X7
FX0N-24MR-ES/UL
0V 24V 0V 24V 0V 24V
Y2 Y3 Y0 Y1 Y5 Y6 Y10 COM0 COM1 COM2 COM3 Y4 COM4 Y7 Y11 Y2 Y3 Y0 Y1 Y5 Y6 Y10 COM0 COM1 COM2 COM3 Y4 COM4 Y7 Y11 Y0 +V0 +V1 Y1 +V2 Y2 +V3 Y3 Y4 Y5 +V4 Y6 Y7 Y10 Y11
FX0N-40MR-ES/UL
0V 24V 0V 24V 0V 24V
Y2 Y10 Y12 Y0 Y1 Y6 Y14 Y16 Y4 COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17 Y2 Y0 Y1 COM0 COM1 COM2 Y3 Y0 +V0 +V1 Y1 +V2 Y2 Y3 +V3 Y10 Y12 Y14 Y16 Y6 Y4 COM3 Y5 Y7 COM4 Y11 Y13 COM5 Y15 Y17 Y4 Y5 Y6 Y7 Y10 Y12 +V4 Y11 Y13 Y14 Y16 +V5 Y15 Y17
FX0N-24MR-DS
FX0N-40MR-DS
FX0N-24MT-DSS
FX0N-40MT-DSS
FX0N-60MT-DSS
+
S/S
S/S X0
X1 X2 X1 X0 X2 X1 X0 X2
X3 X4 X3 X4 X3 X4
X5 X6 X5 X6 X5 X6
X7
X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42
FX0N-60MR-DS
+
S/S
S/S
X7
FX0N-60MR-ES/UL
S/S L N
S/S
X7
FX0N-60MR-ES/UL
0V 24V 0V 24V 0V 24V
Y0 Y6 Y10 Y12 Y20 Y22 Y1 Y2 Y4 Y14 Y16 Y24 Y26 Y7 COM4 Y11 Y13 COM5 Y15 Y17 COM6 Y21 Y23 COM7 Y25 Y27 COM0 COM1 COM2 Y3 COM3 Y5 Y0 Y6 Y10 Y12 Y20 Y22 Y1 Y2 Y4 Y14 Y16 Y24 Y26 Y7 COM4 Y11 Y13 COM5 Y15 Y17 COM6 Y21 Y23 COM7 Y25 Y27 COM0 COM1 COM2 Y3 COM3 Y5 Y0 +V0 +V1 Y1 Y2 +V2 Y3 Y4 +V3 Y5 Y6 Y7 Y10 Y12 +V4 Y11 Y13 Y14 Y16 +V5 Y15 Y17 Y20 Y22 +V6 Y21 Y23 Y24 Y26 +V7 Y25 Y27
FX0N-60MR-DS
FX0N-60MT-DSS
56
MELSEC FX0N/FX2N
Terminal Assignment TERMINALS + DIMENSIONS
Base Units MELSEC FX2N
FX2N-32MT-DSS
S/S
X2 0V X0 X4 X6 X10 X12 X14 X16 24V X1 X3 X5 X7 X11 X13 X15 X17 X2 0V X0 X4 X6 X10 X12 X14 X16 24V X1 X3 X5 X7 X11 X13 X15 X17 X2 0V X0 X4 X6 X10 X12 X14 X16 24V X1 X3 X5 X7 X11 X13 X15 X17 X2 0V X0 X4 X6 X10 X12 X14 X16 24V X1 X3 X5 X7 X11 X13 X15 X17
FX
BASICS
FX2N-32MT-ESS/UL
S/S L N S/S
FX2N-16MT-ESS/UL
S/S L N S/S L N
X6 X4 0V X0 X2 X5 X7 X3 24V X1 X6 X4 0V X0 X2 X5 X7 X3 24V X1
FX2N-32MR-DS
FX2N-16MR-ES/UL
FX2N-32MR-ES/UL
S/S L N
L
N
S/S
0V
X0 X2 X4 X6 24+ X1 X3 X5 X7
L
N
COM X0 X2 X4 X6 X10 X12 X14 X16 24+ X1 X3 X5 X7 X11 X13 X15 X17
01234567
IN
01234567
IN
POWER RUN BATT.V
10 11 12 13 14 15 16 17
POWER RUN BATT.V
FX 2N -16MR
Y0 Y0 Y1 Y1 Y2 Y2 Y3
OUT
01234567
PROG-E CPU-E
FX 2N-32MR
Y0 Y2 COM1 Y1 Y3 Y4 Y6 COM2 Y5 Y7
OUT
01234567 10 11 12 13 14 15 16 17
PROG-E CPU-E
Y3
Y4
Y4
Y5
Y5
Y6
Y6
Y7
Y7
Y10 Y12 Y14 Y16 COM3 Y11 Y13 COM4 Y15 Y17
FX2N-16MR-ES/UL
Y0 Y0 Y0 +V0 +V1 Y1
Y1 Y2 Y1 +V2
Y2 Y3 Y2 +V3
Y3 Y4 Y3 +V4
Y4 Y5 Y4 +V5
Y5 Y6 Y5 +V6
Y6 Y7 Y6 +V7
Y7
FX2N-32MR-ES/UL
Y4 Y0 Y2 Y6 Y10 Y12 Y14 Y16 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM1 Y1 Y4 Y0 Y2 Y6 Y10 Y12 Y14 Y16 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM1 Y1 Y0 +V0 Y0 +V0 Y1 Y1 Y2 Y3 +V1 Y2 Y3 +V1 Y4 Y5 Y4 Y5 Y6 Y7 Y6 Y7 Y10 Y12 +V2 Y11 Y13 Y10 Y12 +V2 Y11 Y13 Y14 Y16 +V3 Y15 Y17 Y14 Y16 +V3 Y15 Y17
FX2N-16MT-ESS/UL
Y7
FX2N-32MR-DS
FX2N-32MT-ESS/UL
FX2N-32MT-DSS
FX2N-48MT-DSS
S/S
X2 0V X0 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X2 0V X0 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X2 0V X0 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X2 0V X0 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27
FX2N-48MT-ESS/UL
S/S L N S/S
FX2N-48MR-DS
FX2N-48MR-ES/UL
S/S L N
FX2N-48MR-ES/UL
Y4 Y0 Y2 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 COM5 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27 COM1 Y1 Y4 Y0 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 COM5 Y2 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 Y21 Y23 Y25 Y27 COM1 Y1 Y0 +V0 Y0 +V0 Y1 Y1 Y2 Y3 +V1 Y2 Y3 +V1 Y4 Y5 Y4 Y5 Y6 Y7 Y6 Y7 Y10 Y12 +V2 Y11 Y13 Y10 Y12 +V2 Y11 Y13 Y14 Y16 Y20 Y22 Y24 Y26 +V4 +V3 Y15 Y17 Y21 Y23 Y25 Y27 Y14 Y16 Y20 Y22 Y24 Y26 +V4 +V3 Y15 Y17 Y21 Y23 Y25 Y27
FX2N-48MR-DS
FX2N-48MT-ESS/UL
FX2N-48MT-DSS
57
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment
FX
BASICS
FX2N-64MT-DSS
+
S/S
X2 0V 0V X0 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X2 0V 0V X0 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X2 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X4 0V 0V X0 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X3 24V 24V X1 X2 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X4 0V 0V X0 X5 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X3 24V 24V X1
FX2N-64MT-ESS/UL
S/S L N S/S
FX2N-64MR-DS
+
FX2N-64MR-ES/UL
S/S L N
S/S L N
0V 24V
0V 24V
X0 X1
X2 X3
X4 X5
X6 X7
X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37
0 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37
10 11 12 13 14 15 16 17
FX2N-64MR
Y0 Y2 COM1 Y1 Y3 Y4 Y6 COM2 Y5 Y7
0
1
2
3
4
5
6
7
20 21 22 23 24 25 26 27 30 31 32 33 34 35 36 37
10 11 12 13 14 15 16 17
Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 COM6 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37
FX2N-64MR-ES/UL
Y4 Y0 Y2 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 COM6 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37 COM1 Y1 Y4 Y0 Y2 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 COM6 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37 COM1 Y1 Y0 +V0 Y0 +V0 Y1 Y1 Y2 Y3 +V1 Y2 Y3 +V1 Y4 Y5 Y4 Y5 Y6 Y7 Y6 Y7 Y10 Y12 +V2 Y11 Y13 Y10 Y12 +V2 Y11 Y13 Y14 Y16 +V3 Y15 Y17 Y14 Y16 +V3 Y15 Y17 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 +V5 +V4 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37 Y20 Y22 Y24 Y26 Y30 Y32 Y34 Y36 +V5 +V4 Y21 Y23 Y25 Y27 Y31 Y33 Y35 Y37
FX2N-64MR-DS
FX2N-64MT-ESS/UL
FX2N-64MT-DSS
FX2N-80MT-DSS
S/S
X2 0V 0V X0 X4 X6 X10 X12 X14 X16 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X2 0V 0V X0 X4 X6 X10 X12 X14 X16 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X2 0V 0V X0 X4 X6 X10 X12 X14 X16 24V 24V X1 X3 X5 X7 X11 X13 X15 X17 X2 0V 0V X0 X4 X6 X10 X12 X14 X16 24V 24V X1 X3 X5 X7 X11 X13 X15 X17
X20 X22 X24 X26 X21 X23 X25 X27 X20 X22 X24 X26 X21 X23 X25 X27 X20 X22 X24 X26 X21 X23 X25 X27 X20 X22 X24 X26 X21 X23 X25 X27
X30 X32 X34 X36 X31 X33 X35 X37 X30 X32 X34 X36 X31 X33 X35 X37 X30 X32 X34 X36 X31 X33 X35 X37 X30 X32 X34 X36 X31 X33 X35 X37
X40 X42 X44 X46 X41 X43 X45 X47 X40 X42 X44 X46 X41 X43 X45 X47 X40 X42 X44 X46 X41 X43 X45 X47 X40 X42 X44 X46 X41 X43 X45 X47
FX2N-80MT-ESS/UL
S/S L N S/S
FX2N-80MR-DS
FX2N-80MR-ES/UL
S/S L N
FX2N-80MR-ES/UL
Y4 Y0 Y2 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 COM1 Y1 Y4 Y0 Y2 Y6 Y10 Y12 Y14 Y16 Y20 Y22 Y24 Y26 Y3 COM2 Y5 Y7 COM3 Y11 Y13 COM4 Y15 Y17 COM5 Y21 Y23 Y25 Y27 COM1 Y1 Y0 +V0 Y0 +V0 Y1 Y1 Y2 Y3 +V1 Y2 Y3 +V1 Y4 Y5 Y4 Y5 Y6 Y7 Y6 Y7 Y10 Y12 +V2 Y11 Y13 Y10 Y12 +V2 Y11 Y13 Y14 Y16 +V3 Y15 Y17 Y14 Y16 +V3 Y15 Y17 Y20 Y22 Y24 Y26 +V4 Y21 Y23 Y25 Y27 Y20 Y22 Y24 Y26 +V4 Y21 Y23 Y25 Y27
Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46 COM6 Y31 Y33 Y35 Y37 COM7 Y41 Y43 Y45 Y47 Y30 Y32 Y34 Y36 Y40 Y42 Y44 Y46 COM6 Y31 Y33 Y35 Y37 COM7 Y41 Y43 Y45 Y47 Y30 Y32 Y34 Y36 +V5 Y31 Y33 Y35 Y37 Y30 Y32 Y34 Y36 +V5 Y31 Y33 Y35 Y37 Y40 Y42 Y44 Y46 +V6 Y41 Y43 Y45 Y47 Y40 Y42 Y44 Y46 +V6 Y41 Y43 Y45 Y47
FX2N-80MR-DS
FX2N-80MT-ESS/UL
FX2N-80MT-DSS
58
Terminal Assignment
FX2N-128MT-ESS/UL
S/S
L
N
0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46 X50 X52 X54 X56 X60 X62 X64 X66 X70 X72 X74 X76 X5 24V 24V X1 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47 X51 X53 X55 X57 X61 X63 X65 X67 X71 X73 X75 X77 X3
FX2N-128MR-ES/UL
S/S
L
N
0V 0V X0 X2 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X30 X32 X34 X36 X40 X42 X44 X46 X50 X52 X54 X56 X60 X62 X64 X66 X70 X72 X74 X76 X5 24V 24V X1 X7 X11 X13 X15 X17 X21 X23 X25 X27 X31 X33 X35 X37 X41 X43 X45 X47 X51 X53 X55 X57 X61 X63 X65 X67 X71 X73 X75 X77 X3
S/S
L
0 10 11 12 13 14 15 16 17 30 31 32 33 34 35 36 37 50 51 52 53 54 55 56 57 70 71 72 73 74 75 76 77 1 2 3 4 5 6 7 20 21 22 23 24 25 26 27 40 41 42 43 44 45 46 47 60 61 62 63 64 65 66 67
N
X2 0V 0V X0 X4 X6 X10 X12 X14 X16 X20 X22 X24 X26 X1 24V 24V X3 X5 X7 X11 X13 X15 X17 X21 X23 X25
X30 X32 X34 X36 X40 X42 X44 X46 X50 X52 X54 X56 X60 X62 X64 X66 X70 X72 X74 X76 X27 X31 X33 X35 X37 X41 X43 X45 X47 X51 X53 X55 X57 X61 X63 X65 X67 X71 X73 X75 X77
0 10 11 12 13 14 15 16 17 30 31 32 33 34 35 36 37 50 51 52 53 54 55 56 57 70 71 72 73 74 75 76 77
FX2N-128MR
1
2
3
4
5
6
7
20 21 22 23 24 25 26 27
40 41 42 43 44 45 46 47 60 61 62 63 64 65 66 67
FX2N-128MR-ES/UL
Y0 Y2 COM2 Y5 Y7 Y10 Y12 COM4 Y15 Y17 Y20 Y22 Y24 Y26 COM6 Y31 Y33 Y35 Y37 Y40 Y42 Y44 Y46 COM8 Y51 Y53 Y55 Y57 Y60 Y62 Y64 Y66 COM10 Y71 Y73 Y75 Y77 Y3 Y4 Y6 COM3 Y11 Y13 Y14 Y16 COM5 Y21 Y23 Y25 Y27 Y30 Y32 Y34 Y36 COM7 Y41 Y43 Y45 Y47 Y50 Y52 Y54 Y56 COM9 Y61 Y63 Y65 Y67 Y70 Y72 Y74 Y76 COM1 Y1
FX2N-128MT-ESS/UL
Y0
Y2
+V1
Y5
Y7
+V0
Y1
Y3
Y4
Y6
Y10 Y12 +V3 Y15 Y17 Y20 Y22 Y24 Y26 +V5 Y31 Y33 Y35 Y37 Y40 Y42 Y44 Y46 +V7 Y51 Y53 Y55 Y57 Y60 Y62 Y64 Y66 +V9 Y71 Y73 Y75 Y77 +V2 Y11 Y13 Y14 Y16 +V4 Y21 Y23 Y25 Y27 Y30 Y32 Y34 Y36 +V6 Y41 Y43 Y45 Y47 Y50 Y52 Y54 Y56 +V8 Y61 Y63 Y65 Y67 Y70 Y72 Y74 Y76
TERMINALS + DIMENSIONS
FX
MELSEC FX0N/FX2N
BASICS
59
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment
Compact Extension Units MELSEC FX0N
FX
BASICS
FX0N-40ET-DSS
+
S/S
S/S X0
X1 X2
X3 X4
X5 X6
X7 X0
X1 X2
X3 X4
X5 X6
X7 X0
X1 X2
X3 X4
X5 X6
X7
FX0N-40ER-DS
+
X3 COM COM X1 X3 X3 X5 X7 X1 X5 X7 X1 X5 X7 X2 X2 X2 X0 X4 X6 X0 X4 X6 X4 X6 X0 X3 COM COM X1 X3 X3 X5 X7 X1 X1 X5 X5 X7 X7 X2 X2 X2 X0 X4 X6 X0 X4 X4 X6 X6 X0
FX0N-40ER-ES/UL
L
N
X1
X3
X5
X7
X1
X3
X5
X7
FX0N-40ER-ES/UL
COM 24V COM 24V COM 24V
Y2 Y0 Y6 Y0 Y1 Y6 Y2 Y4 Y4 COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y1 Y3 COM5 Y5 Y7 Y2 Y0 Y6 Y0 Y1 Y6 Y2 Y4 Y4 COM0 COM1 COM2 Y3 COM3 Y5 Y7 COM4 Y1 Y3 COM5 Y5 Y7 Y0 +V0 +V1 Y1 +V2 Y2 Y3 +V3 Y4 Y5 Y6 Y7 +V4 Y0 Y1 Y2 Y3 +V5 Y4 Y5 Y6 Y7
FX0N-40ER-DS
FX0N-40ET-DSS
Modular Extension Units MELSEC FX0N
+V0 Y0 Y1 Y2 Y3 +V1 Y5 Y7 Y6 Y4 COM2 Y5 Y7 Y6 Y4 X5 X4 X3 X2 X6 X7
FX0N-8EYT-ESS/UL
FX0N-16EYT-ES/UL
+V0 Y0
Y1 Y2
Y3
+V1 Y5 Y7 Y4 Y6 COM2 Y5 Y7 Y6 Y4 X5 X4 X6 X7
FX0N-8EYR-ES/UL
Y3 COM1 Y1 Y0 Y2 S/S X0 S/S X0 X1 X1 X2 X3
FX0N-16EYR-ES/UL
Y3 COM1 Y1 Y0 Y2 S/S X0 X1 X2 X3
FX0N-8EX-ES/UL
FX0N-16EX-ES/UL
FX0N-8ER-ES/UL
COM Y1 Y3 Y0 Y2
S/S
X0
X1
X2
X3
X4
X5
X6
X7
POWER
IN 01234567 01234567
X0
X1
X2
X3
X4
X5
X6
X7
FX0N-16EX-ES/UL
X0 X1
X2 X3
X4 X5
X6 X7
FX0N-16EYR-ES/UL
Y0 Y2 Y3 COM3 Y1 Y0 +V2 Y1 Y2 Y3
Y6 Y4 COM4 Y5 Y7 Y4 +V3 Y5 Y6 Y7
FX0N-16EYT-ES/UL
60
MELSEC FX0N/FX2N
Terminal Assignment TERMINALS + DIMENSIONS
Compact Extension Units MELSEC FX2N
FX
BASICS
FX2N-32ET-ESS/UL
S/S L N S/S L N
0V X0 X2 X4 X6 X0 X2 X4 X6 24V X1 X3 X5 X7 X1 X3 X5 X7 0V X0 X2 X4 X6 X0 X2 X4 X6 24V X1 X3 X5 X7 X1 X3 X5 X7
FX2N-32ER-ES/UL
L
N
S/S
0V
X0 X2 X4 X6 X0 X2 X4 X6 X1 X3 X5 X7 24+ X1 X3 X5 X7
01234567
IN
10 11 12 13 14 15 16 17
POWER RUN BATT.V
FX 2N-32ER
Y0 Y2 Y3 COM1 Y1 Y4 Y6 COM2 Y5 Y7
OUT
01234567 10 11 12 13 14 15 16 17
PROG-E CPU-E
Y10 Y12 Y14 Y16 COM3 Y11 Y13 COM4 Y15 Y17
FX2N-32ER-ES/UL
Y4 Y0 Y2 Y6 Y0 Y2 Y4 Y6 Y3 COM2 Y5 Y7 COM3 Y1 COM1 Y1 Y3 COM4 Y5 Y7 Y0 +V0 Y1 Y2 Y3 +V1 Y4 Y5 Y6 Y7 +V2 Y0 Y1 Y2 Y3 +V3 Y4 Y5 Y6 Y7
FX2N-32ET-ESS/UL
FX2N-48ET-DS
S/S
X6 X4 X2 X0 X6 X4 X2 X0 X6 X4 0V X0 X2 X7 X5 X3 X1 X7 X5 X3 X1 X7 X5 X3 24V X1 X6 X4 X2 X0 X6 X4 X2 X0 X6 X4 0V X0 X2 X7 X5 X3 X1 X7 X5 X3 X1 X7 X5 X3 24V X1 X6 X4 X2 X0 X6 X4 X2 X0 X6 X4 0V X0 X2 X7 X5 X3 X1 X7 X5 X3 X1 X7 X5 X3 24V X1 X6 X4 X2 X0 X6 X4 X2 X0 X6 X4 0V X0 X2 X7 X5 X3 X1 X7 X5 X3 X1 X7 X5 X3 24V X1
FX2N-48ET-ES/UL
S/S L N S/S
FX2N-48ER-DS
FX2N-48ER-ES/UL
S/S L N
FX2N-48ER
FX2N-48ER-ES/UL
Y4 Y0 Y6 Y0 Y2 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5 Y3 COM2 Y5 Y7 COM3 Y1 COM1 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7 Y4 Y0 Y6 Y0 Y2 Y2 Y4 Y6 Y0 Y2 Y4 Y6 COM5 Y7 COM3 Y1 Y3 COM2 Y5 COM1 Y1 Y3 COM4 Y5 Y7 Y1 Y3 Y5 Y7 Y0 +V0 Y0 +V0 Y1 Y1 Y2 Y3 +V1 Y2 Y3 +V1 Y4 Y5 Y4 Y5 Y6 Y7 +V2 Y6 Y7 +V2 Y0 Y1 Y0 Y1 Y2 Y3 +V3 Y2 Y3 +V3 Y4 Y5 Y4 Y5 Y6 Y7 Y6 Y7 Y0 Y1 Y0 Y1 Y2 Y3 Y2 Y3 Y4 Y5 Y4 Y5 Y6 Y7 Y6 Y7 +V4 +V4
FX2N-48ER-DS
FX2N-48ET-ES/UL
FX2N-48ET-DS
61
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment
Modular Extension Units MELSEC FX2N
FX
BASICS
FX2N-16EX-ES/UL
IN 0
1 2 3 4 5 6 7
FX2N-16EYT-ESS/UL
S/S X0 X1 X2 X3 X5 X6 X7 X0 X4
X1 X2 X3 X4 X5
OUT 0
1 2 3 4 5 6 7
S/S X0
+V0
+V0 Y0 Y1 Y2 Y3 Y5 Y6 Y7 Y0 Y4
Y0 Y1 Y2 Y3 Y4 Y5
POWER
POWER
X6 X7 X0 X1
Y6 Y7 Y0
FX 2N -16EX
IN 0
1 2 3 4 5 6 7
Y1
X1 X3 X5 X7 X2 X4 X6
ES
FX 2N -16EYT
OUT 0
1 2 3 4 5 6 7
Y1 Y3 Y5 Y7 +V1 Y2 Y4 Y6
X2 X3 X4 X5 X6 X7
Y2 Y3 Y4 Y5 Y6 Y7 +V1
FX2N-16EYR-ES/UL
OUT 0
1 2 3 4 5 6 7
Y0 Y2 Y4 COM1 Y1 Y3 Y5
COM1 Y0 Y1 Y2 Y3 Y5 Y6 Y7 Y0 Y4
POWER
Y6 Y7 Y0 Y1
FX 2N -16EYR
OUT 0
1 2 3 4 5 6 7
Y1 Y3 Y5 Y7 COM2 Y2 Y4 Y6
Y2 Y3 Y4 Y5 Y6 COM2 Y7
62
MELSEC FX0N/FX2N
Terminal Assignment TERMINALS + DIMENSIONS
Special Function Modules MELSEC FX0N / FX2N
FX
BASICS
FX0N-16NT
24 + 24G FG 24 + 24G ECM
SDA SDB SG RDA RDB SG
FX0N-3A
V IN 2 I IN 2 COM V IN 1 I IN 1 COM
V OUT I OUT COM
FX0N-485ADP
24 + 24G FG 24 + 24G FG
SDA SDB SG RDA RDB SG
FX0N-32NT-DP
24G 24+ FG
24G 24+ FG
POWER
DC
RUN
BF
DIA
FX2N-232IF
24+
24-
FX0N-232ADP
24+ 24-
FX 2N -232IF
POWER SD RD
FX 2N -232IF
63
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Terminal Assignment
FX
BASICS
Special Function Modules MELSEC FX2N
24+ 24V+ VII+
POWER
24+ 242424+ CH1 VII+
POWER
24+
24-
V+ VII+
CH1
V+
V+ VII+
FG V+ VII+ FG
CH3 CH2
FG V+ VII+ FG
V+ VII+
CH2 CH3
V+ VII+
FX 2N -4AD
VIFG
24 V A/D
V+
FX 2N -4DA
VI-
V+
V+ VII+
V+ VI-
FX2N-4AD
FX2N-4DA
I+
I+ V+ I+
I+
24 V D/A
FG V+ VI-
CH4
CH4
V+ VI-
VI-
VI-
V+ I+
I+
I+
24+ 24L+
POWER
24+ 242424+ 24+ 24-
SLD L-
L+
POWER
IL-
CH1 L+
CH1
SLD L-
IL+ L-
FG L+ SLD LCH3
FG
L+ FG
IL-
CH2
CH2
SLD LSLD
IL+
L+
LFG CH3
FX 2N-4AD-TC
L+
SLD
FX 2N-4AD-PT
L+ FG
24 V A/D
I-
IL+
L+ L-
FX2N-4AD-TC
FX2N-4AD-PT
L-
L24 V A/D
LIL-
FG
CH4
CH4
SLD
I-
L+
SLD L-
L+
L+
L+
L-
L-
UP DOWN A B
A12+ AB12+ B24+ A24+ A5+
A12+ A- B12+ A24+ A5+ B24+
VIN COM0 FP RP PG0PG0+
COM0 RP PG0+ VIN FP PG0-
POWER
BB5+ XD5 XD24 COMD
FX 2N -1PG
POWER
S TDP OOG P GO
1PG POWER
BXD5 COMD
B5+ XD24 XP24
FX 2N -1HC
COMP
DIS PRE YH YS
XP24
FRCE PPLR RR
COMP YH- YS-
CLR STOP DOG COM1 S/S S/S
COM1 S/S S/S CLR STOP DOG
FX2N-1HC
XP5 YH+ YS+
YHYS-
XP5 YH+ YS+
64
MELSEC FX0N/FX2N
Terminal Assignment TERMINALS + DIMENSIONS
Special Function Modules MELSEC FX
FX
BASICS
FX-16NT
24G +24 FG
FX-16NP
24G 24+ FG
FX-16NT
RDB SDB RDA SDA SG
FX-16NT-S3
+24 24G FG +24 24G FG
FX-16NP-S3
+24 24G FG +24 24G FG
FX-16NT-S3
SDA SDB RDA RDB SG
65
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Dimensions
Dimensions of Base Units and Compact Extension Units MELSEC FX0N
FX
BASICS
X X -10
87
Type FX0N-24MR-DS FX0N-24MR-ES/UL FX0N-24MT-DSS FX0N-40MR-DS X (in mm) 130 130 130 150 150 150 185 185 185 150 150
MITSUBISHI
90
80 35
FX0N-40MR-ES/UL FX0N-40MT-DSS FX0N-60MR-DS FX0N-60MR-ES/UL FX0N-60MT-DSS FX0N-40ER-DS FX0N-40ER-ES/UL
MELSEC FX0N-24MR-ES
o4,5
Dimensions of Modular Extension Units and Special Function Modules MELSEC FX0N
X o4,5
87
Type FX0N- 8ER-ES/UL FX0N-8EX-ES/UL FX0N-8EYR-ES/UL
_ FXON 16NT
X (in mm) 43 43 43 43 70 70 70 43 43 43 43 43
FX0N-8EYT-ESS/UL
35
90 80
POWER POWER - DC - RUN - ERR.
FX0N-16EX-ES/UL FX0N-16EYR-ES/UL FX0N-16EYT-ES/UL FX0N-232ADP FX0N-3A
4
FX0N-16NT FX0N-32NT-DP FX0N-485ADP
66
MELSEC FX0N/FX2N
Dimensions TERMINALS + DIMENSIONS
Dimensions of Base Units MELSEC FX2N
FX
BASICS
X X -10
87
Base Units
Type FX2N-16M FX2N-32M X (in mm) 130 150 182 220 285 350
L
N
S/S
0V
X0 X2 X4 X6 X0 X2 X4 X6 X1 X3 X5 X7 24+ X1 X3 X5 X7
01234567
FX2N-48M
POWER
IN
10 11 12 13 14 15 16 17
FX2N-64M
80
90
RUN BATT.V OUT
01234567 10 11 12 13 14 15 16 17
35
FX2N-80M FX2N-128M
PROG-E CPU-E
FX 2N-32ER
Y2 Y0 COM1 Y1 Y3 Y4 Y6 COM2 Y5 Y7
Y10 Y12 Y14 Y16 COM3 Y11 Y13 COM4 Y15 Y17
o4,5
Dimensions of Compact and Modular Extension Units MELSEC FX2N
X o4,5
IN 0
1 2 3 4 5 6 7
87
Compact Extension Units
Type FX2N-32ER-ES/UL FX2N-32ET-ESS/UL FX2N-48ER-DS FX2N-48ER-ES/UL X (in mm) 150 150 182 182 182
POWER
90 80
FX 2N-16EX
IN 0
1 2 3 4 5 6 7
35
FX2N-48ET-DSS
Modular Extension Units
Type FX2N-16EX-ES/UL FX2N-16EYR-ES/UL FX2N-16EYT-ESS/UL X (in mm) 40 40 40
4
67
MELSEC FX0N/FX2N
TERMINALS + DIMENSIONS Dimensions
Dimensions of Special Function Modules MELSEC FX2N
FX
BASICS
X o4,5
87
Special Function Modules FX2N
Type FX2N- 4DA FX2N-4AD FX2N-4AD-TC X (in mm) 55 55 55 55 55 43 55
POWER
FX2N-4AD-PT
35
90 80
FX2N-1HC FX2N-1PG-E FX2N-232-IF
FX 2N-4AD
24 V A/D
4
Dimensions of Special Function Modules MELSEC FX
A
C
Special Function Modules FX
Type FX-16NP, FX-16NT FX-16NP-S3, FX-16NT-S3 A x B x C (in mm) 45 x 140 x 95 73 x 140 x 95
68
35
B
MELSEC FX0N/FX2N
Dimensions TERMINALS + DIMENSIONS
FX
BASICS
69
MELSEC FX
PROGRAMMING Software
Programming and Documentation Software for Standard Personal Computers
FX
BASICS
With MELSEC MEDOC, MELSEC MEDOC FX/WIN and MELSEC MEDOC plus, MITSUBISHI ELECTRIC offers a programming and documentation system which makes your personal computer into an
efficient programming and documentation system for all controllers of the MELSEC FX series.
To take account of the importance of programming, all program packages permit efficient and time-saving programming.
MELSEC MEDOC
In MELSEC MEDOC, convenient editing functions are accessible through a clearly laid out menu. The fast, convenient creation and processing of PLC programs are performed by means of either a contact plan or a list of instructions. In addition to versatile monitor and test functions, MELSEC MEDOC has an extensive Help menu.
Software Series Language Format Order information F-Set E 3,5" FX,FX0, FX0S,FX0N English 3,5" Art. no. 56123
By connecting a standard printer, it is possible to produce input/output lists and cross reference lists for documentation. The software is supplied complete with an SC-09N serial interface cable for connecting the PLC to one of the PC's serial ports.
F-Set G 3,5" FX,FX0, FX0S,FX0N German 3,5" 56124
FX0-Set E FX0,FX0S English 3,5" / 5,25" 32712
FX0-Set G FX0,FX0S German 3,5" / 5,25" 32787
MELSEC MEDOC FX/WIN
MELSEC MEDOC FX/WIN is the standard programming software for the MELSEC FX familiy and combines all functions of MELSEC MEDOC with the user guidance of Microsoft Windows(R). MELSEC MEDOC FX/WINprovides the user with facilities for structured programming, function modules and many different diagnostic functions. This software posseses all Windows(R)-specific benefits and is especially geared to the new FX2N series. The software is supplied complete with an SC-09N serial interface cable, which is used for the connection between the PLC and a serial interface of a personal computer. MELSEC MEDOC plus can be run under Windows 3.11 and Windows 95.
Software Series Language Format Order information MM FX/WIN Whole FX family Englisch 3,5" diskettes Art. no. 70536
MELSEC MEDOC plus
MELSEC MEDOC plus provides all functions of the pre-mentioned programs and meets the programming standard for the future: IEC 1131.3. This makes MELSEC MEDOC plus ready for the programming standard of the future and offers in addition the basis for the on-leading programming of the MELSEC A and Q series.
Software Series Language Format Order information F-Set E Whole FX family English 3,5" diskettes Art. no. 56118
MELSEC MEDOC plus can be run under Windows 3.11 and Windows 95. The software is supplied complete with an SC-09N serial interface cable.
F-Set G Whole FX family German 3,5" diskettes 56117
70
MITSUBISHI ELECTRIC
MELSEC FX
Software PROGRAMMING
Parameter Software for Profibus Networks and Process Supervision System for all Mitsubishi PLCs
F X
BASICS
MELSEC ProfiMap
MELSEC ProfiMap V2.0 is a user friendly configurations software for open networks like MAP 3.0/ETHERNET and PROFIBUS/DP or PROFIBUS/FMS. The software package is a 32 bit application for Windows 95 and Windows NT4.0. Configuration of all PROFIBUS modules for the MELSEC series is possible. Due to the supported extended user parameters of a GSD file, easy parameter setting of PROFIBUS/DP slave devices is possible even for third party devices.
Full version V2.0 Supported master modules for the Mitsubishi Profibus/DP: A1SJ71PB92D,AJ71PB92D Profibus/FMS:A1SJ71PB96F,AJ71PB96F MELSEC AnS/QnAS and A/Q series MAP3.0/Ethernet: AJ71M56EF2 Language English Configuration cable ProfiCab is included Disk type 3,5" disks Order information Art. no. 102996
Software
Update V1.0 to V2.0 Profibus/DP: A1SJ71PB92D,AJ71PB92D Profibus/FMS: A1SJ71PB96F,AJ71PB96F MAP3.0/Ethernet: AJ71M56EF2 English ProfiCab is not included 3,5" disks 102997
MELSEC MX SCADA
MELSEC MX SCADA is a process visualisation system that can handle everything from simple installations to complex production control systems. The software package can administer up to 100000 objects. A variety of interfaces are supported, including ETHERNET. The software runs under Windows 95 and Windows NT and is available in a variety of different
Software Series Language Disk type Order information
Development version All MELSEC PLC Englisch CD ROM Art. no. on request
Run-time version All MELSEC PLC Englisch CD ROM on request
DEMO version All MELSEC PLC Englisch CD ROM 65135
MITSUBISHI ELECTRIC
71
MELSEC FX
PROGRAMMING Hand-Held Programming Units - Cables - EPROM Writer
Hand-Held Programming Unit FX-10 P-E and FX-20 P-E
FX
BASICS
These small hand-held programming units designed for industry have a user-friendly keyboard and a clearly laid out, back-lit LC display. On both programming units, the MELSEC FX family is programmed in the list of instructions. The FX-20P has an integrated CMOS-RAM with capacitor buffering.
This ensures storage of the PLC program and its duplication, for example for series machines.
Specifications General specifications Ambient temperature Ambient relative humidity (non-condensing) Power supply Current consumption Display Character display Connectable PLC Key board Memory Data security Cable, is adjoint Weight Dimensions(WxHxD) Order information
FX-10 P-E Conforms to base units FX2N,FX0N,FX0S 0 - 40 C 35 - 85 % V DC 5 5 % by PLC mA 120 LCD 16 x 2 FX0,FX0S,FX,FX0N,FX2N* keys 35 -- -- -- kg 0.25 mm 85x160x27 Art. no. 32538
FX-20 P-E 0 - 40 C 35 - 85 % DC 5 5 % by PLC 150 LCD (backlight) 16 x 4 FX0,FX0S,FX,FX0N,FX2N* 35 8000 steps PLC-program Data is safed up to 3 days by capacitor. FX-20P-CAB 0.4 90 x 170 x 30 23802 *Version 3.0 or higher
Connection Cable and Adapter Cable
With the adapter cable FX-20P-CADP, the peripheral units of the FX series are connected to units of the FX0, FX0S and FX0N series.
Data Cable Length For connecting to controller Order information FX-20P-CAB type Connection cable cm 150 FX Art. no. 30815 FX-20P-CAB0 Connection cable 300 FX0S,FX2N,FX0N 55917 FX-20P-CABP Adapter cable 20 FX0S,FX2N,FX0N 31870
EPROM Writer FX-20 P-RWM
The EPROM writer FX-20 P-RWM is plugged directly into the hand-held programming unit FX-20 P-E. It is used for transferring the PLC programs of the MELSEC FX controller to the EPROM memory cassette FX-EPROM-8. Conversely, existing programs can be read from the FX-EPROM-8 memory cassette into the CMOS-RAM of the controller and program comparisons carried out.
W PO
ER ITE
WR
FX-2
0P-R
WM
Data Order information
FX-20 P-RWM Art. no. 23818
72
MITSUBISHI ELECTRIC
MELSEC FX
PROFIBUS Connector PROGRAMMING
ProfiCon Profibus Connector
The ProfiCon bus connector plug is designed for connecting DIN 19245 standard Profibus components with data transfer rates of up to 12 Mbaud. The connector is available with or without a selectable termination resistor.
Specifications Data rate 12 Mbit/s Terminator Order information ProfiCon supported No Art. no. 64127 ProfiConT supported Yes (selectable) 87035
F X
BASICS
ProfiC
on
MITSUBISHI ELECTRIC
73
MELSEC FX
ORDER FORM
MITSUBISHI ELECTRIC EUROPE B.V. Factory-Automation / German Branch Gothaer Str. 8 D-40880 Ratingen Fax: +49 2102 486-717
Order declaration
Pos. Number Item (type) Article number
Company: Department: Street: Address: Phone: Fax:
...................... ...................... ...................... ...................... ...................... ......................
Description
Remarks
Notes when ordering: When ordering, please use only the type designations and order numbers shown in this catalogue.
74
MITSUBISHI ELECTRIC
MELSEC FX
INDEX
Adapter cable . . . . . . . . . . . . . . . . . . . . . . . . . 72 Base units FX0S series . . . . . . . . . . . . . . . . . . . . . . . . FX0N series . . . . . . . . . . . . . . . . . . . . . . . . FX2N series . . . . . . . . . . . . . . . . . . . . . . . . Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 26 28 54
Combination possibilities . . . . . . . . . . . . . . 21 Compact extension units. . . . . . . . . . . . . . . 32 Connection cable. . . . . . . . . . . . . . . . . . . 55, 72 Configuration FX0N/FX2N series . . . . . . . 24 CR01-R2/R4 SET . . . . . . . . . . . . . . . . . . . . . . . 52 CR01-R4/R4 . . . . . . . . . . . . . . . . . . . . . . . . . . . 52 Description of units FX0S series . . . . . . . . . . . . . . . . . . . . . . . . FX0N/FX2N series . . . . . . . . . . . . . . . . . . Dimensions FX0S series . . . . . . . . . . . . . . . . . . . . . . . . FX0N series . . . . . . . . . . . . . . . . . . . . . . . . FX2N series . . . . . . . . . . . . . . . . . . . . . . . . Digital I/Os . . . . . . . . . . . . . . . . . . . . . . . . . . . . EPROM writer. . . . . . . . . . . . . . . . . . . . . . . . . . EPROM/EEPROM cassettes . . . . . . . . . . . . . Extension units compact. . . . . . . . . . . . . . . . . . . . . . . . . . . modular . . . . . . . . . . . . . . . . . . . . . . . . . . . F2-40BL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-10 P-E. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-16NP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-16NP-S3 . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-16NT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-16NT-S3. . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-20 P-CAB . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-20 P-CAB0. . . . . . . . . . . . . . . . . . . . . . . . . . FX-20 P-CABP. . . . . . . . . . . . . . . . . . . . . . . . . . FX-20 P-E. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-20 P-RWM. . . . . . . . . . . . . . . . . . . . . . . . . . FX-65EC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-485PC-IF . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-EPROM-8. . . . . . . . . . . . . . . . . . . . . . . . . . . FX-EEPROM-4 . . . . . . . . . . . . . . . . . . . . . . . . . FX-EEPROM-4C . . . . . . . . . . . . . . . . . . . . . . . . FX-EEPROM-8 . . . . . . . . . . . . . . . . . . . . . . . . . FX-RAM-8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-RAM-8C . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX-ROM SOC1 . . . . . . . . . . . . . . . . . . . . . . . . . FX-RTC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX0-10LDR . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX0N-3A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX0N-8ER-ES/UL . . . . . . . . . . . . . . . . . . . . . . . FX0N-8EX-ES/UL . . . . . . . . . . . . . . . . . . . . . . . FX0N-8EYR-ES/UL. . . . . . . . . . . . . . . . . . . . . . FX0N-8EYT-ESS/UL. . . . . . . . . . . . . . . . . . . . . FX0N-16EX-ES/UL. . . . . . . . . . . . . . . . . . . . . . FX0N-16EYR-ES/UL . . . . . . . . . . . . . . . . . . . . FX0N-16EYT-ESS/UL . . . . . . . . . . . . . . . . . . . FX0N-16NT . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX0N-24MR-DS . . . . . . . . . . . . . . . . . . . . . . . . FX0N-24MR-ES/UL . . . . . . . . . . . . . . . . . . . . . FX0N-24MT-DSS . . . . . . . . . . . . . . . . . . . . . . . FX0N-32NT-DP . . . . . . . . . . . . . . . . . . . . . . . . 11 20 17 66 67 31 72 52 32 34 54 72 44 44 44 44 72 72 72 72 72 55 47 52 52 52 52 52 52 53 52 15 36 34 34 34 34 34 34 34 43 26 26 26 49
FX0N-40B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX0N-40ER-DS . . . . . . . . . . . . . . . . . . . . . . . . FX0N-40ER-ES/UL . . . . . . . . . . . . . . . . . . . . . FX0N-40ET-DSS . . . . . . . . . . . . . . . . . . . . . . . FX0N-40MR-DS. . . . . . . . . . . . . . . . . . . . . . . . FX0N-40MR-ES/UL. . . . . . . . . . . . . . . . . . . . . FX0N-40MT-DSS. . . . . . . . . . . . . . . . . . . . . . . FX0N-60MR-DS. . . . . . . . . . . . . . . . . . . . . . . . FX0N-60MR-ES/UL. . . . . . . . . . . . . . . . . . . . . FX0N-60MT-DSS. . . . . . . . . . . . . . . . . . . . . . . FX0N-232ADP . . . . . . . . . . . . . . . . . . . . . . . . . FX0S-10MR-DS . . . . . . . . . . . . . . . . . . . . . . . . FX0S-10MR-ES/UL . . . . . . . . . . . . . . . . . . . . . FX0S-10MT-DSS . . . . . . . . . . . . . . . . . . . . . . . FX0S-14MR-DS . . . . . . . . . . . . . . . . . . . . . . . . FX0S-14MR-ES/UL . . . . . . . . . . . . . . . . . . . . . FX0S-14MT-DSS . . . . . . . . . . . . . . . . . . . . . . . FX0S-20MR-DS . . . . . . . . . . . . . . . . . . . . . . . . FX0S-20MR-ES/UL . . . . . . . . . . . . . . . . . . . . . FX0S-20MT-DSS . . . . . . . . . . . . . . . . . . . . . . . FX0S-30MR-DS . . . . . . . . . . . . . . . . . . . . . . . . FX0S-30MR-ES/UL . . . . . . . . . . . . . . . . . . . . . FX0S-30MT-DSS . . . . . . . . . . . . . . . . . . . . . . . FX2N-1HC. . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-1PG-E . . . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-4AD. . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-4AD-PT . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-4AD-TC . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-4DA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-8AV-BD . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-16EX-ES/UL . . . . . . . . . . . . . . . . . . . . . FX2N-16EYR-ES/UL . . . . . . . . . . . . . . . . . . . . FX2N-16EYT-ES/UL . . . . . . . . . . . . . . . . . . . . FX2N-16MR-ES/UL. . . . . . . . . . . . . . . . . . . . . FX2N-16MT-ESS/UL. . . . . . . . . . . . . . . . . . . . FX2N-32ER-ES/UL . . . . . . . . . . . . . . . . . . . . . FX2N-32ET-ESS/UL . . . . . . . . . . . . . . . . . . . . FX2N-32MR-DS. . . . . . . . . . . . . . . . . . . . . . . . FX2N-32MR-ES/UL. . . . . . . . . . . . . . . . . . . . . FX2N-32MT-DSS. . . . . . . . . . . . . . . . . . . . . . . FX2N-32MT-ESS/UL. . . . . . . . . . . . . . . . . . . . FX2N-48ER-DS . . . . . . . . . . . . . . . . . . . . . . . . FX2N-48ER-ES/UL . . . . . . . . . . . . . . . . . . . . . FX2N-48ET-DSS . . . . . . . . . . . . . . . . . . . . . . . FX2N-48ET-ESS/UL . . . . . . . . . . . . . . . . . . . . FX2N-48MR-DS. . . . . . . . . . . . . . . . . . . . . . . . FX2N-48MR-ES/UL. . . . . . . . . . . . . . . . . . . . . FX2N-48MT-ESS/UL. . . . . . . . . . . . . . . . . . . . FX2N-48MT-DSS. . . . . . . . . . . . . . . . . . . . . . . FX2N-64MR-DS. . . . . . . . . . . . . . . . . . . . . . . . FX2N-64MR-ES/UL. . . . . . . . . . . . . . . . . . . . . FX2N-64MT-DSS. . . . . . . . . . . . . . . . . . . . . . . FX2N-64MT-ESS/UL. . . . . . . . . . . . . . . . . . . . FX2N-80MR-DS. . . . . . . . . . . . . . . . . . . . . . . . FX2N-80MR-ES/UL. . . . . . . . . . . . . . . . . . . . . FX2N-80MT-ESS/UL. . . . . . . . . . . . . . . . . . . . FX2N-80MT-DSS. . . . . . . . . . . . . . . . . . . . . . . FX2N-128MR-ES/UL . . . . . . . . . . . . . . . . . . . FX2N-128MT-ESS/UL . . . . . . . . . . . . . . . . . . FX2N-232BD . . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-232IF . . . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-422BD . . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-485ADP . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-485BD . . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-CNV-BD . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-CNV-IF . . . . . . . . . . . . . . . . . . . . . . . . . . FX2N-EEPROM-16 . . . . . . . . . . . . . . . . . . . . .
54 32 32 32 26 26 26 27 27 27 40 12 12 12 12 12 12 13 13 13 13 13 13 39 39 37 38 38 37 36 35 35 35 28 28 33 33 28 28 28 28 33 33 33 33 29 29 29 29 29 29 29 29 30 30 30 30 30 30 41 40 41 46 46 50 50 52
General specifications FX0S series . . . . . . . . . . . . . . . . . . . . . . . . . 12 FX0N/FX2N series . . . . . . . . . . . . . . . . . . 25 Input-SIM: FX0S/FX0N . . . . . . . . . . . . . . . . . . 14 Input-SIM: FX2N. . . . . . . . . . . . . . . . . . . . . . . . 53 Interface converter . . . . . . . . . . . . . . . . . . . . . 52 MELSEC MEDOC. . . . . . . . . . . . . . . . . . . . . . . . 70 MELSEC MEDOC plus . . . . . . . . . . . . . . . . . . . 70 MELSEC MEDOC plus tutorial . . . . . . . . . . . 70 MELSECNET/MINI . . . . . . . . . . . . . . . . . . . . . . 42 Memory cassettes . . . . . . . . . . . . . . . . . . . . . . 52 Model designation code. . . . . . . . . . . . . . . . 11 Modular extension units . . . . . . . . . . . . . . . . 34 MX SCADA software . . . . . . . . . . . . . . . . . . . . 71 Networks (overview) . . . . . . . . . . . . . . . . . . . . 8 1:n multidrop . . . . . . . . . . . . . . . . . . . . . . 45 MELSECNET/MINI. . . . . . . . . . . . . . . . . . . 42 Parallel link. . . . . . . . . . . . . . . . . . . . . . . . . 45 Peer-to-peer . . . . . . . . . . . . . . . . . . . . . . . 45 PROFIBUS/DP . . . . . . . . . . . . . . . . . . . . . . 48 Power consumption. . . . . . . . . . . . . . . . . . . . 23 Profibus plug . . . . . . . . . . . . . . . . . . . . . . . . . . 73 ProfiMap software. . . . . . . . . . . . . . . . . . . . . . 71 Programming units. . . . . . . . . . . . . . . . . . . . . 72 Programm loader . . . . . . . . . . . . . . . . . . . . . . 15 PROM adapter . . . . . . . . . . . . . . . . . . . . . . . . . 53 Real-time clock cassette . . . . . . . . . . . . . . . . 52 Simulation box. . . . . . . . . . . . . . . . . . . . . 14, 53 Simulation strip . . . . . . . . . . . . . . . . . . . . 14, 53 Special function modules analog modules . . . . . . . . . . . . . . . . . . . . 36 common description . . . . . . . . . . . . . . . 22 communications modules . . . 43, 46, 50 PROFIBUS modules . . . . . . . . . . . . . . . . . 49 interface modules . . . . . . . . . . . . . . 40, 46 counter/positioning modules . . . . . . . 39 System description general . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 FX0S series . . . . . . . . . . . . . . . . . . . . . . . . . 10 FX0N series . . . . . . . . . . . . . . . . . . . . . . . . 18 FX2N series . . . . . . . . . . . . . . . . . . . . . . . . 19 System specifications FX0S series . . . . . . . . . . . . . . . . . . . . . . . . . 13 FX0N/FX2N series . . . . . . . . . . . . . . . . . . 25 Terminal assignment FX0S series . . . . . . . . . . . . . . . . . . . . . . . . . 16 FX0N extension units . . . . . . . . . . . . . . . 60 FX2N extension units . . . . . . . . . . . . . . . 61 FX0N base units . . . . . . . . . . . . . . . . . . . . 56 FX2N base units . . . . . . . . . . . . . . . . . . . . 57 Special function modules . . . . . . . . . . . 63
MITSUBISHI ELECTRIC
75
FA CENTER MITSUBISHI ELECTRIC CORPORATION Mitsubishi Denki Bldg. Marunouchi Tokyo 100 JAPAN Phone: (03) 3218-3176 Fax: (03) 3218-2422 MITSUBISHI ELECTRIC EUROPE B.V. Factory Automation Gothaer Strae 8 D-40880 Ratingen Germany Phone: (0 21 02) 486-0 Fax: (0 21 02) 4 86-1 12 MITSUBISHI ELECTRIC EUROPE EUROPE B.V. Industrial Division Travellers Lane GB-Hatfield Herts. AL10 8 XB Great Britain Phone: (0 17 07) 27 61 00 Fax: (0 17 07) 27 86 95 MITSUBISHI ELECTRONICS AMERICA, INC. Industrial Automation Division 800 Biermann Court Mt. Prospect, IL 60056 United States of America Phone: (708) 298-9223 Fax: (708) 298-1834 Ryoden (Holdings) Ltd. 10th Fl., Manulife T., 169 Electric Rd., N. Point Hong Kong Phone: 2887-8870 Fax: 2578-2461 JAPAN
EUROPEAN REPRESENTATIVES GEVA GmbH Wiener Strae 89 A-2500 Baden Phone: (0 22 52) 8 55 52-0 Fax: (0 22 52) 4 88 60 GETRONICS NV/SA Pontbeeklaan 43 B-1731 Zellik Phone: (02) 4 67 17 51 Fax: (02) 4 67 17 45 INEA CR d.o.o. Drvinje bb HR-10000 Zagreb Phone: (01) 36 71 40 Fax: (01) 36 71 40 UK AUTOCONT s.r.o. Nemocnicni 12 CZ-70100 Ostrava 1 Phone: (0 69) 6 15 21 11 Fax: (0 69) 6 11 35 62 ELPEFA A/S Geminivej 32 DK-2670 Greve Phone: (0 43) 95 95 95 Fax: (0 43) 95 95 90 AUSTRIA
EUROPEAN REPRESENTATIVES MITSUBISHI ELECTRIC IRELAND EUROPE B.V. - Irish Branch Westgate Business Park IRL-Dublin 22 Phone: (1) 450 50 07 Fax: (1) 456 13 37 CARPANETO & C. S.p.A. ITALY Via Ferrero 10 I-10090 Cascine Vica-Rivoli (TO) Phone: (0 11) 95 90 111 Fax: (0 11) 95 90 250 Geveke Electronics bv NETHERLANDS Donauweg 10 NL-1043 AJ-Amsterdam Phone: (0 20) 5 86 15 92 Fax: (0 20) 5 86 19 27 Beijer Electronics A/S Teglverksveien 1 N-3002 Drammen Phone: (32) 24 30 00 Fax: (32) 84 85 77 MPL Technology SP. Z.o.o ul. Wroclawska 53 PL-30011 Krakow Phone: (0 12) 632 28 85 Fax: (0 12) 632 47 82 NORWAY
EUROPEAN REPRESENTATIVES GTS TURKEY Fahri Gizden Sokak, Hacaloglu Apt. No. 22/6 TR-80280 Gayrettepe/Istanbul Phone: (2 12) 267 40 11 Fax: (2 12) 266 14 50
BELGIUM
EUROPE
MIDDLEEASTREPRESENTATIVE TEXEL Electronics Ltd. P.O. Box 6272 IL-Netanya 42160 Phone: (09) 863 08 91 Fax: (09) 885 24 30 ISRAEL
CROATIA
CZECHIA
DENMARK
POLAND
USA
MITSUBISHI ELECTRIC ENGLAND EUROPE B.V. - UK Branch Travellers Lane GB-Hatfield Herts. AL10 8 XB Phone: (0 17 07) 27 61 00 Fax: (0 17 07) 27 86 95 UTU ELEKTROTEHNIKA Laki 12 E EE-0006 Tallinn Phone: (06) 563 194 Fax: (06) 563 836 Beijer Electronics OY Elannontie 5 FIN-01510 Vantaa Phone: (09) 615 20 11 Fax: (09) 615 20 500 ESTONIA
F. Fonseca Lda PORTUGAL Estrada de Taboeira 87/89, Esgueira P-3800 Aveiro Phone: (0 34) 31 58 00 Fax: (0 34) 31 58 04 TUINGDOR 20, Fierarilor Street RO-72126 Bucaresti Phone: (01) 211 98 01 Fax: (01) 210 71 81 INEA d.o.o. Ljubljanska 80 SI-61230 Domzale Phone: (0 61) 71 80 00 Fax: (0 61) 72 16 72 ROMANIA
HONG KONG
FINLAND
SLOVENIA
P.T. SAHABAT INDONESIA INDONESIA Blok A/Utara No. 1 Kav, No. 11 Jakarta 11050 Indonesia Phone: 6610651 Fax: 6603700 SETSUYO ENTERPRISE Co.,Ltd. TAIWAN TAIWAN 3rd Fl., No.122, Wu Kung 2nd Road Wu-Ku Hsiang Taipei Hsien Taiwan Phone: (02) 298 - 17 95 Fax: (02) 298 - 18 25 MITSUBISHI ELECTRIC SALE SINGAPORE SINGAPORE Pte. Ltd. Industrial Engineering Center No. 6, Commonwealth Lane #01 - 01 149547 Singapore Phone: 476 - 72 35 Fax: 476 - 74 39
IP Systemes FRANCE 8, Rue Colonel Chambonnet F-69672 Lyon Bron Phone: (04) 72 14 18 00 Fax: (04) 72 14 18 01 MITSUBISHI ELECTRIC GERMANY EUROPE B.V. - German Branch Gothaer Strae 8 D-40880 Ratingen Phone: (0 21 02) 486-0 Fax: (0 21 02) 4 86-1 12 GEVA Kft Tamasi Aron u. 34 H-1124 Budapest Phone: (01) 3 75 38 98 Fax: (01) 3 75 06 88 HUNGARY
Medicion y Control, S.A. SPAIN Gr. Via d. l. Corts Catalanes 133, 4 E-08014 Barcelona Phone: (03) 4 22 77 00 Fax: (03) 4 32 28 47 Beijer Electronics AB Box 325 S-20123 Malmo Phone: (0 40) 35 86 00 Fax: (0 40) 93 23 01 SWEDEN
ECONOTEC AG SWITZERLAND Postfach 282 CH-8309 Nurensdorf Phone: (01) 838 48 11 Fax: (01) 838 48 12
Specifications subject to change. Art.no.68544-B,Printed in Germany 12.98
MITSUBISHI ELECTRIC EUROPE B.V.
F AC TO R Y AU TO M A T I O N
GOTHAER STR. 8, D-40880 RATINGEN, TEL. (0 21 02) 4 86-0, FAX (0 21 02) 4 86-1 12 www.mitsubishi-automation.com