 3286-20
CLAMP ON POWER HiTESTER
Power measuring instruments
All Powerful
Effective input current level
1.00 A to 1000 A
W VA var
600.0kW max.(1o)
COS
1.000 (90.0) 1.000 (90.0)
Harmonics
Up to 20th Up to
C A T III 6 0 0 V
http://www.hioki.co.jp/
1
80 mm 20 mm
busbar max.
Functionality and Safety
Applications
Use as a single-phase power meter Voltage
1o Power meter mode
Source
o 55 mm max.
AC
RMS
600 Vrms max.
V
Effective power/ voltage/ current
Load
Current
AC
RMS
1000 Arms max.
A
This displays the result of vector calculations on PT/CT conversion ratio settings are not possible. single-phase power.
Apparent/ reactive power
Power factor
(effective value power factor)
Power
VA var
600.0kW max.(1o)
W
RST
Phase detection Measure phase on a single-phase line
1o Power Factor meter mode
The phase angle between the voltage waveform and the current waveform is found, and the power factor (cos o) and reactivity (sin o) are calculated and displayed.
Normal/ Reverse/ Missing
Power factor (cos o)
Power factor
COS
o
1.000 (90.0)
Peak
Peak
Reactivity (sin o)
Phase angle (o)
1700 A peak max.
value
Frequency
Hz
1000 Hz max.
The 3286-20 provides the following 2 types of power factor measurement. If the waveform includes harmonic distortion, there will be a difference between the two measurement values, and the method must be selected accordingly. qPower factor derived by phase discrimination (cos o):
1o Power Factor meter and 3o Power Factor meter mode From the phase information for the fundamental frequency component, cos o is calculated. This is suitable for assessing the quality of a power supply.
Harmonics
Harmonics
Up to 20th
qPower factor (effective value power factor) derived from effective power / apparent power: 1o Power meter mode
This is calculated from the power value including harmonic components (effective power / apparent power). This is suitable for evaluating the performance of standalone load equipment and similar cases.
* It is not possible to calculate the effective power factor of a three-phase line.
2
Packed into a Handheld Unit
Helpful battery capacity check
Whenever the unit is powered on, and while the record function is operating, the battery capacity can be checked to avoid battery exhaustion during measurement.
Simple checking of three-phase lines
3o Power Factor meter mode
Source
For harmonic suppression
Harmonic measurement function
Harmonics effective value/ total harmonic distortion Harmonics effective value/ harmonic percentage
Load
Power factor (cos o)
Phase angle (o) Reactivity (sin o)
Harmonic coefficients Total harmonic distortion Ex. THD-R is 65.9% Ex. Fundamental
component is 40.3 A
Harmonic coefficients Harmonic percentage
Ex. 3rd order is 33.7 A Ratio to case in which fundamental component is 100%
Balanced three-phase power can also be displayed
The analysis values for coefficients for each of the harmonics from 1 to 20 of voltage or current can be displayed.
Effective power/ voltage/ current Apparent/ reactive power
Phase detection
External output of data
Output to PC
(Optional 9636-01 required)
check
The 3286-20's three-phase power measurement method calculates and displays the power values for a sine wave input at 50/60 Hz, assuming it is balanced and there is no distortion. Accurate measurement is not possible on a three-phase line if it is not balanced, for example when controlled by an inverter or thyristor.
Since there is no integration function, it is not possible to measure total energy consumed (Wh).
Cord length: approx 2m
Check power supply fluctuations
Max. and min. value displays
Using the record function, it is possible to check the amplitude of fluctuations.
Record elapsed time
Example: 4 h 25 m
Data output connector RS-232C interface by optical insulating coupler q OS:Windows 95, 98, NT4.0, 2000, Me*1 q Connector: D-sub 9 pin q Fetch interval: 6s/30s/1m/5m/10m. q Buffer size: 32,700 max.
Care must be taken with regard to battery life
*1. Windows is a registered trademark of Microsoft Corporation.
Printer output to 9442 (optional)
The output is sent to the printer each time the 3286-20 HOLD key is pressed.
(For about 1 sec.) q Printing method: Thermal serial dot matrix q Paper width: 112 mm q Printing speed: 52.5cps q Power supply: 9443 AC ADAPTER or supplied nickelhydride battery (capable of printing about 3000 lines on full charge from 9443) q Dimensions and mass: 160W 66.5H 170D mm; 580 g 9636 9443-02 RS-232C CABLE AC ADAPTER (For the EU) 9443-03 (For the America)
V
Waveform display is not available Care must be taken with regard to battery life
Record peak value fluctuations Easily check peak value fluctuations.
Please note that waveforms with amplitudes at or less than 250ms cannot be detected accurately
+
0
-
Waveform display is not available
Cord length approx 1.3m Not for use with Model 3286-20
3
s Basic specifications
Measurement items : Voltage, current, voltage/current peak, effective/ reactive / apparent power(Single-phase or 3-phase), power factor, reactivity, phase angle, frequency, phase detection(3phase), voltage/current harmonic levels(up to 20th) Measurable conductor diameter : o55mm (2.16"), 80 mm 20 mm busbar max. : LCD, digital (6000 counts) Display Rectification method : RMS (true root mean square value) Display update rate : NORMAL approx. 1 time/ sec, SLOW 1 time/ 3-sec at HARM meas. approx. 1 time/ 2-sec Analog response time : 4.0 seconds or less (when input is changed from 0% to 90% of range.)
[Power factor/ Phase angle/ Reactivity measurement]
Detection method : Power factor (cos o) : : Phase angle Reactivity (sin o) : Phase discrimination by phase detection (zero crossing) 0.000 (lead) to 1.000 to 0.000 (lag) 90.0(lead) to 0.0to 90.0(lag) 0.000 (lead) to 1.000 to 0.000 (lag)
[Frequency measurement] Effective in the voltage and current functions
Measurement range : 30.0 Hz to 100 Hz (at 100.0 Hz range) 100 Hz to 1000Hz (at 1000 Hz range) Min. input level : Voltage 10 Vrms-sine wave, Current 1 Arms-sine wave
[Voltage/ Current/ Power measurement]
[Wave peak measurement] Effective in the voltage and current functions
Range Table
AC Voltage
AC Current
20.00 A
6.000 kW
200.0 A
30.00 kW 60.00 kW 60.00 kW 120.0 kW
1000 A
150.0 kW 300.0 kW 300.0 kW 600.0 kW 600.0 kW
150.0 V 300.0 V 600 V
Single-phase 3.000 kW
*3-phase (balanced load)
Measurement range : 150 (375 peak) / 300 (750 peak) / 600 (1020 peak) V 20 (50 peak) / 200 (500 peak) / 1000 (1700 peak) A Effective Input Range : Effective value of sine wave is within effective input permissible in the range and within circuit dynamic
[Harmonic measurement] Effective in the voltage and current functions
Measurement items : Level of each order, percentage of each order and total harmonic distortion (THD-F and THD-R) Measurement range : Fundamental frequency 50 / 60 Hz Window width : 1 cycle (50 / 60 Hz), Data points: 256 points Window type : Rectangular Orders analyzed : Up to 20th
Single phase 6.000 kW
*3-phase (balanced load) 6.000/12.00 kW 60.00/120.0 kW
Single phase 12.00 kW
*3-phase 240.0 kW 600.0/1200 kW (balanced load) 24.00 kW *3-phase power is calculated and displayed on the basis of a balanced, 50/60 Hz, sine wave input. For apparent power and reactive power, the unit of watts in the above table is replaced by VA and var respectively.
[Other functions]
Phase detection : Normal/ reverse/ missing (at 3-phase balanced load) : MAX. value and MIN. value (Effective in the voltage, Record current and effective / apparent power functions) Battery capacity : Displayed in % when the unit is powered on : Holds display Data hold Auto power off : Approx. 10 minutes, buzzer sounds just before power is turned off, can be extended or cancelled : RS-232C interface by optical insulating coupler Data output
Effective value P.F. : Max. allowable current : Max. usable circuit voltage : Effective input range :
0.000 (lead) to 1.000 to 0.000 (lag); 1o only 1000 Arms cont. 600 Vrms (insulated conductor) Voltage: 10 V to 600 V, Current: 1 A to 1000A, Power: 80 V to 600 V and 1 A to 1000 A Min. Display value : Voltage: 0.6 Vrms, Current: 0.06 Arms Display indication range : 5 or less are zero-suppressed, and the upper limit is to 125% of the range setting (to 100% for the 1000 A range) (RMS value) Circuit dynamic : 2.5 or less (1000 A and 600 V range is 1.7 or less)
s Measurement accuracy (23 C5 C (73F 9F), Less than 80%rh., sine wave input, power factor = 1)
[Voltage/ Current/ Power measurement] 30 Hz to 45 Hz 45 Hz to 66 Hz 66 Hz to 1 kHz Voltage 1.5 %rdg.5 dgt. 1.0 %rdg.3 dgt. Current Power
not rated
1.5%rdg.5 dgt.
1.3 %rdg.3 dgt. 2.0 %rdg.5 dgt.
Accuracy guaranteed only for 50/60 Hz (COS o=1)
Single-phase: 2.3 %rdg.5 dgt. 3-phase: 3.0 %rdg.10 dgt.(at balanced load)
: 0.3 % rdg.1 dgt. (at 100.0Hz range) 1.0 % rdg.1 dgt. (at 1000Hz range) : 3.0 %rdg.5 dgt. (45 Hz to 1 kHz) Wave peak Thermal coefficient : Voltage and current: within 0.1Accuracy/ C (0 to 40C) Phase: within 2 (0 to 40C) Conductor position : Within 0.7 % in any direction from the center of sensor External magneticfield : 400A/m corresponds to 1.00 A max. Power factor influence : 10.0 % f.s. (cos o=0.5) : Order Harmonics Order Accuracy Accuracy Frequency
1 2 to 6 7, 8
: 3 Phase angle Power factor (cos o) : 32 dgt.
s General Specifications
Applicable standards : Safety EN61010-1:1992+A2:1995 CAT III 600V EN61010-2-031:1996, EN61010-2-032:1995 EN60529:1991 IP40 : EMC EN61326-1:1997+A1:1998+A2:2001 Withstand voltage : 5.55 kV AC between clamp and frame, between (50/60 Hz, 1 minute) clamp and circuitry
3.0 %rdg.10 dgt. 3.5 %rdg.10 dgt. 4.5 %rdg.10 dgt.
9, 10 11 to 15 16 to 20
5.0 %rdg.10 dgt. 7.0 %rdg.10 dgt. 10.0 %rdg.10 dgt.
Measurement method : Digital sampling method Operating temperature : 0C to 40C, 80%rh or less, no condensation Storage temperature : -10C to 50C, no condensation Power supply : 6LR61 alkaline battery1 (continuous operation max. 25 hours) (9V battery) 6F22 manganese battery1 (continuous operation max. 10 hours) Dimensions, mass : Approx 100 W 287 H 39 D mm, Approx 650g
(Approx 3.94(W )11.3 (H)1.54 (D), Approx 22.6 oz.)
3286-20 CLAMP ON POWER HiTESTER
(Includes 9635 VOLTAGE CORD, 9245 CARRYING CASE, HAND STRAP)
Options 9635-01 VOLTAGE CORD 9636-01 RS-232C PACKAGE 9442 PRINTER
9636 9443-02 9443-03 1196 RS-232C CABLE (For 9442 printer) AC ADAPTER (For 9442 printer, EU) AC ADAPTER (For 9442 printer, America) RECORDING PAPER (For printer, 10 rolls)
9635-01
Cord length approx 3m
Cord length approx 3m
When ordering the 9442 PRINTER, also order the 9636 RS-232C CABLE required for connection to the 3286-20, and 9443 AC ADAPTER.
DISTRIBUTED BY
HEAD OFFICE : 81 Koizumi, Ueda, Nagano, 386-1192, Japan TEL +81-268-28-0562 / FAX +81-268-28-0568 E-mail: os-com@ hioki.co.jp HIOKI USA CORPORATION : 6 Corporate Drive, Cranbury, NJ 08512 USA TEL +1-609-409-9109 / FAX +1-609-409-9108 E-mail: hioki@ hiokiusa.com
Shanghai Representative Office : 1704 Shanghai Times Square Office 93 Huaihai Zhong Road Shanghai, 200021, P.R.China TEL +86-21-6391-0090, 0092 FAX +86-21-6391-0360 E-mail: info@hioki.cn
All information correct as of Oct. 3, 2003. All specifications are subject to change without notice.
328620E2-3XB-05K
Printed in Japan


▲Up To Search▲   

 
Price & Availability of 3286-20

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X